The emergency generator is a diesel generator of its own, in a room above the main deck and away from the engine room, so a fire or flooding there cannot reach it too. When the main switchboard loses power, it starts by itself and takes over the emergency switchboard within 45 seconds. It has its own fuel tank, enough for 18 hours on a cargo ship and 36 hours on a passenger ship, and its own starting arrangement.
It supplies only the emergency loads: emergency lighting, the emergency fire pump, the steering gear, the fire detection system, radio and navigation equipment, and the general alarm.
Those 45 seconds are a long time in the dark. A transitional source, batteries or a UPS, keeps the most vital services, such as emergency lighting, navigation lights, alarms and internal communications, alive from the moment the power goes until the emergency generator takes over. It must be able to carry them for at least half an hour. A passenger ship must always have one. A cargo ship needs one unless its emergency generator starts by itself and takes the load within 45 seconds. Separate batteries also power the GMDSS radio equipment.
In port or in dry dock, the ship can stop its generators and take power from shore through a shore connection box, with a cable from the shore supply. Before the shore breaker is closed, three things are checked.
- Voltage: the same as the ship's system.
- Frequency: the same as the ship's, since a 60 Hz ship on a 50 Hz supply would run every motor slow.
- Phase sequence: correct, or every motor on board would run backwards. A phase sequence indicator at the shore connection shows it.
An interlock stops the shore supply being connected while the ship's generators are on the busbars. Some ports now supply ships with power at high voltage while they are alongside, so they can switch their engines off: this is called cold ironing.