Shore and emergency power

The emergency generator and its 45-second start, the batteries that bridge the gap, and the three checks before connecting shore power.

Power distribution, page 10 of 102 min readUpdated 4 November 2026All 10 pages

A ship has more than one way to get power. Its own generators most of the time; an emergency generator when they fail; batteries to bridge the gap; and shore power in port or in dry dock.

An interactive shore connection loads here. It needs JavaScript; the sections below explain everything it shows.

The emergency generator

The emergency generator is a diesel generator of its own, in a room above the main deck and away from the engine room, so a fire or flooding there cannot reach it too. When the main switchboard loses power, it starts by itself and takes over the emergency switchboard within 45 seconds. It has its own fuel tank, enough for 18 hours on a cargo ship and 36 hours on a passenger ship, and its own starting arrangement.

It supplies only the emergency loads: emergency lighting, the emergency fire pump, the steering gear, the fire detection system, radio and navigation equipment, and the general alarm.

Transitional battery supply

Those 45 seconds are a long time in the dark. A transitional source, batteries or a UPS, keeps the most vital services, such as emergency lighting, navigation lights, alarms and internal communications, alive from the moment the power goes until the emergency generator takes over. It must be able to carry them for at least half an hour. A passenger ship must always have one. A cargo ship needs one unless its emergency generator starts by itself and takes the load within 45 seconds. Separate batteries also power the GMDSS radio equipment.

Shore power

In port or in dry dock, the ship can stop its generators and take power from shore through a shore connection box, with a cable from the shore supply. Before the shore breaker is closed, three things are checked.

  1. Voltage: the same as the ship's system.
  2. Frequency: the same as the ship's, since a 60 Hz ship on a 50 Hz supply would run every motor slow.
  3. Phase sequence: correct, or every motor on board would run backwards. A phase sequence indicator at the shore connection shows it.

An interlock stops the shore supply being connected while the ship's generators are on the busbars. Some ports now supply ships with power at high voltage while they are alongside, so they can switch their engines off: this is called cold ironing.

Check yourself
1. How quickly must the emergency generator take over?
Within 45 seconds.
2. What keeps emergency lighting on during those seconds?
The transitional source: batteries or a UPS.
3. Name the three checks before closing onto shore power.
Voltage, frequency and phase sequence.

Going for your ETO CoC oral?

The full Shore and emergency power notes (T04), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • SOLAS Chapter II-1, regulations 42 and 43: the emergency source of power for passenger and cargo ships, its location, the services it supplies, fuel for 36 hours (passenger) and 18 hours (cargo), and the transitional source: always on a passenger ship (42.3.1.3), and on a cargo ship unless the emergency generator starts automatically and takes the load within 45 s (43.3.1.3); regulation 44: automatic starting of the emergency generator.
  • Fernandez, E.A. Marine Electrical Technology, chapter 4, emergency power and shore supply: the location of the emergency source apart from the main one (p.116-117); the transitional source, an accumulator battery carrying emergency lights, navigation lights, watertight door circuits and internal communications for at least half an hour (4.1.8, p.125).
  • Elec-Buddy notes: T16 SOLAS (emergency source, 45 s auto-start, 30-minute transitional source), T04 Switchboards (shore connection checks and the shore supply interlock, cold ironing).
  • The lab is a 440 V, 60 Hz ship taking power from shore, with the three checks on this page and the interlock against the ship's generators. Its pump is a 4-pole motor, whose speed follows 120 f รท p, 1,800 rpm at 60 Hz and 1,500 rpm at 50 Hz (the Induction motor page); slip is ignored. Fernandez (p.130) describes the remedy for a reversed sequence: interchange any two leads at the connection box, with the shore supply off.