Protection relays

Overcurrent and short circuit protection, reverse power, voltage and frequency, earth fault, preferential trip and differential protection, in plain terms.

Power distribution, page 4 of 103 min readUpdated 4 November 2026All 10 pages

A protection relay watches a circuit and decides when to trip it. It measures current, voltage, power or frequency, compares them with its settings, and if something is wrong it tells the breaker to open. Good protection trips only the faulty part and leaves the rest of the ship running.

Two interactive generators with their protection loads here. It needs JavaScript; the sections below explain everything it shows.

Overcurrent and short circuit

The most common protection. For an overload it waits before tripping, and the higher the current, the shorter the wait: an inverse time curve, often called IDMT. A separate instantaneous element trips at once on the very large current of a short circuit.

The settings are graded so the breaker nearest the fault trips first. A fault on one motor trips only that motor's feeder, not the generator.

Reverse power

When generators run in parallel and one loses its engine power, it stops supplying power and starts taking it from the others, running as a motor. The reverse power relay sees power flowing the wrong way and trips that generator's breaker, before it drags the others down.

Typical settings for a diesel generator are 5 to 15% of its rated power, with a delay of 0.5 to 2.5 seconds, so that a moment of reverse power while paralleling does not trip it.

Voltage and frequency
  • Undervoltage: trips a generator breaker when its voltage is lost, and stops it closing onto a dead machine.
  • Under and over frequency: a sign that a generator's engine is struggling or running away.
Earth fault

On an insulated 440 V system an earth fault is usually alarmed rather than tripped, so the supply carries on. On high voltage systems with an earthed neutral, earth fault relays trip the faulty circuit.

Preferential trip

This guards against losing the whole ship. When a generator is close to overload, the preferential trip sheds the least important loads, such as the galley or air conditioning, in stages, so the generator can keep the essential ones running instead of tripping and blacking out the ship.

A common arrangement: the preference trip picks up at about 110% of the generator's rated current, sheds the first group, such as air conditioning, galley and laundry, after 5 seconds, and the second, such as reefer containers, after 10 seconds. The generator's own overcurrent trip is set higher and slower, at about 150% after 20 seconds, so the preference trip always gets the first chance.

Differential

Mainly on large and high voltage generators and transformers. It compares the current going into the machine with the current coming out. They should be equal; any difference means current is escaping through a fault inside, and it trips at once.

Check yourself
1. What does a reverse power relay protect against?
A generator that has lost its engine power running as a motor, taking power from the others.
2. A generator nears overload. What sheds load to save it?
The preferential trip, which drops the least important loads in stages.
3. What does "graded" protection achieve?
The breaker nearest the fault trips first, so only the faulty part is lost.

Going for your ETO CoC oral?

The full Protection relays notes (T04), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), chapter 3, generators and main circuit breakers (from p.49): generator protection, overcurrent, reverse power, undervoltage and preferential tripping; the preference trip at 110% shedding in stages after 5 and 10 s, and the generator overcurrent trip at 150% after 20 s (p.20); reverse power settings of 5-15% with 0.5-2.5 s for a diesel (p.135).
  • Fernandez, E.A. Marine Electrical Technology, chapter 13, fault protection devices (from p.489): the induction-disc inverse time relay (p.506) and protection discrimination and selective coordination (13.15, p.537).
  • Elec-Buddy notes: T04 Switchboards (IDMT overcurrent relay, reverse power relay, preferential trip in stages, differential protection).
  • The lab uses Hall's settings: reverse power at 8% after 2 s, inside the 5-15% and 0.5-2.5 s he gives for a diesel (p.135); the preference trip picking up at 110% and shedding in stages after 5 s and 10 s, and the generator overcurrent trip at 150% after 20 s (p.20). The loads are illustrative. An automated test checks the sequence.