Two interactive generators with their protection loads here. It needs JavaScript; the sections below explain everything it shows.
The most common protection. For an overload it waits before tripping, and the higher the current, the shorter the wait: an inverse time curve, often called IDMT. A separate instantaneous element trips at once on the very large current of a short circuit.
The settings are graded so the breaker nearest the fault trips first. A fault on one motor trips only that motor's feeder, not the generator.
When generators run in parallel and one loses its engine power, it stops supplying power and starts taking it from the others, running as a motor. The reverse power relay sees power flowing the wrong way and trips that generator's breaker, before it drags the others down.
Typical settings for a diesel generator are 5 to 15% of its rated power, with a delay of 0.5 to 2.5 seconds, so that a moment of reverse power while paralleling does not trip it.
- Undervoltage: trips a generator breaker when its voltage is lost, and stops it closing onto a dead machine.
- Under and over frequency: a sign that a generator's engine is struggling or running away.
On an insulated 440 V system an earth fault is usually alarmed rather than tripped, so the supply carries on. On high voltage systems with an earthed neutral, earth fault relays trip the faulty circuit.
This guards against losing the whole ship. When a generator is close to overload, the preferential trip sheds the least important loads, such as the galley or air conditioning, in stages, so the generator can keep the essential ones running instead of tripping and blacking out the ship.
A common arrangement: the preference trip picks up at about 110% of the generator's rated current, sheds the first group, such as air conditioning, galley and laundry, after 5 seconds, and the second, such as reefer containers, after 10 seconds. The generator's own overcurrent trip is set higher and slower, at about 150% after 20 seconds, so the preference trip always gets the first chance.
Mainly on large and high voltage generators and transformers. It compares the current going into the machine with the current coming out. They should be equal; any difference means current is escaping through a fault inside, and it trips at once.