High voltage

What counts as HV on a ship, why large ships use 3.3, 6.6 or 11 kV, what is different about the equipment, and why HV work is handled differently.

Power distribution, page 9 of 102 min readUpdated 4 November 2026All 10 pages

On ships, high voltage means above 1,000 V AC. Large ships, such as big container ships, cruise ships, LNG carriers and those with electric propulsion, generate at 3.3 kV, 6.6 kV or 11 kV, and use transformers to bring it down to 440 V for everything else.

An interactive comparison of system voltages loads here. It needs JavaScript; the sections below explain everything it shows.

Why high voltage is used

For the same power, a higher voltage needs a lower current, since power is voltage times current. Raise the voltage fifteen times, from 440 V to 6.6 kV, and the current for the same load falls to one fifteenth. That brings three gains.

  • Smaller cables, since conductor size is set by current.
  • Smaller fault currents, so the breakers and busbars do not have to stand the enormous currents a very large 440 V system would make.
  • Lower losses, since cable heating goes with the square of the current.

On a small ship these gains are not worth the cost of high voltage equipment and the extra safety precautions. On a big one they are essential.

HV equipment
  • Breakers: vacuum or SF6 breakers instead of air breakers.
  • Earthing: the system is usually earthed through a neutral earthing resistor, so earth faults trip.
  • Insulation: thicker, with screens on the cables to control the electric field.
HV safety

High voltage can jump through the air to a hand or a tool that only comes close, and a fault can release an arc flash of enormous heat. So nobody works on high voltage equipment without a permit to work, a trained and authorised person in charge, the equipment isolated, proved dead and earthed with earthing switches or leads, and the right protective equipment.

Isolated is not enough on high voltage. A cable or capacitor can hold a dangerous charge after it is switched off, and induced voltages can appear from nearby live circuits. That is why high voltage equipment is earthed before anyone touches it.
Check yourself
1. What counts as high voltage on a ship?
Above 1,000 V AC.
2. Going from 440 V to 6.6 kV, what happens to the current for the same power?
It falls to about one fifteenth.
3. Why is HV equipment earthed before work, not only isolated?
It can hold a charge, and pick up induced voltages, after it is switched off.

Going for your ETO CoC oral?

The full High voltage notes (T02), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), chapter 8, electric propulsion and high voltage: LV below 1,000 V, HV above it, typically 3.3 or 6.6 kV with 11 kV on some ships (p.146); higher voltage to cut both the load and the fault currents, with the 6 MW example at 440 V and 6.6 kV (p.146-147); vacuum and SF6 breakers (p.166); the neutral earthing resistor limiting earth fault current (p.167); HV safety rules, the permit to work, and earthing down before work (p.168-170).
  • Elec-Buddy notes: T02 High Voltage (HV basics, VCB and SF6, the NER, arc flash, HV permit to work and earthing down).
  • The lab feeds the same load at 440 V, 3.3, 6.6 and 11 kV at a power factor of 0.8, using P = √3 × V × I × cos φ. The cable is illustrative: each three-core cable is taken to carry up to 400 A, with 0.01 Ω per phase for the whole feeder, so that the numbers of cables and the losses can be compared. An automated test checks its figures against the page.