Fuses

How a fuse works, how an HRC fuse puts out the arc in quartz sand, current limiting, where fuses are used on board and why the rating matters.

Power distribution, page 3 of 102 min readUpdated 4 November 2026All 10 pages

A fuse is the simplest protection there is. A short, thin link that melts when too much current passes, and breaks the circuit. Once it has blown it has to be replaced, but it is cheap, fast and certain.

An interactive HRC fuse loads here. It needs JavaScript; the sections below explain everything it shows.

Principle of operation

The current through the fuse heats its element, as it would any conductor. At normal current the element stays below its melting point. Too much current heats it until it melts, and the circuit is broken. The bigger the overcurrent, the faster it melts: a small overload takes a long time, a short circuit only a fraction of a cycle.

Every fuse has a minimum fusing current: the smallest current that will ever melt it. Below that the element reaches a steady temperature and stays there, however long the current flows. The ratio of that current to the fuse's rating is its fusing factor. A cartridge fuse with a fusing factor of 1.5 and a 100 A rating will carry 140 A indefinitely, and blow at anything over 150 A.

fusing factor = minimum fusing current รท current rating
for cartridge fuses, not more than 1.5
The HRC fuse

On a ship's power circuits the fuses are HRC, high rupturing capacity, fuses. The element, usually silver, sits inside a strong ceramic body packed with fine quartz sand. When it melts on a short circuit, the arc that forms melts the sand around it into glass, which absorbs the heat and puts the arc out quickly and safely inside the body.

On a big fault it is so fast that it breaks the current before it can rise to its full value. That is called current limiting, and it protects the cables and equipment downstream from the full force of the fault.

Applications on board
  • Motor starters: HRC fuses for short circuit protection, with the overload relay handling overloads.
  • Back-up for breakers on circuits where a fault could be larger than the breaker can break.
  • Drives and electronics: very fast semiconductor fuses that protect thyristors and IGBTs.
  • Control circuits and instruments: small cartridge fuses.
Always replace a fuse with one of the same rating and type. A bigger fuse may not blow before the cable overheats. And find out why it blew before you replace it: a fuse that blows again straight away is telling you there is still a fault.
Check yourself
1. What is the sand in an HRC fuse for?
It melts into glass round the arc, absorbing its heat and putting it out safely inside the body.
2. What does "current limiting" mean?
The fuse breaks a fault before the current reaches its full value.
3. A 10 A fuse keeps blowing. Why not fit a 20 A one?
The cable may not be rated for 20 A and could overheat; and the real fault is still there.

Going for your ETO CoC oral?

The full Fuses notes (T04), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Fernandez, E.A. Marine Electrical Technology, chapter 13, fault protection, including co-ordination between fuses, contactor and overcurrent relay (13.16.1, p.542); the fusing factor and minimum fusing current, and a fusing factor not over 1.5 for cartridge fuses (pp.533-534).
  • Elec-Buddy notes: T04 Switchboards (HRC fuse construction and current limiting), T08 Electronics (semiconductor fuses).
  • The lab is a teaching model of a 100 A cartridge fuse, not a maker's curve. Its fusing factor is 1.5, the most Fernandez gives for a cartridge fuse (pp.533-534); how fast it heats, and the size of its notches, are illustrative, chosen so the overload and the short circuit both show at a watchable speed. An automated test checks its figures against the page.