No insulation is perfect. Put a voltage across it and a very small current flows, some through the material and some across its surface. The insulation resistance, IR, is that voltage divided by that current. In healthy insulation it is huge, hundreds or thousands of megohms (MΩ). Moisture, dirt, oil, heat and age all bring it down.
Insulation fails gradually. A falling IR, recorded test after test, gives warning long before a winding burns out or a cable fails to earth.
An insulation tester, often called a megger, is a resistance meter that tests at a high DC voltage, so that it stresses the insulation the way the working voltage does. A multimeter's few volts would tell you nothing.
| Equipment | Test voltage |
|---|---|
| Ship's equipment rated 440 V AC | 500 V DC |
| High voltage equipment | 1,000 V or 5,000 V DC; 5,000 V for 6.6 kV |
The equipment must first be switched off, isolated, locked off and proved dead. Prove the tester itself first: with its two leads shorted together and the test button pressed, it should read zero.
On a three-phase motor, test each phase to earth, between the frame and each winding in turn, and then between the phases. A standard spot test is applied for one minute. Testing while the machine is still warm from running gives the most realistic reading, because insulation leaks more when it is hot.
For equipment up to 1,000 V, the minimum acceptable IR is usually 1 MΩ. For high voltage, a common rule is one megohm per kilovolt, plus one:
These are minimums, not targets. Healthy insulation often reads up to a hundred times the minimum, and what matters most is how a reading compares with the last ones from the same machine.
When a test voltage is applied, the reading does not settle at once. In good, dry insulation it keeps rising for minutes, as the insulating material slowly absorbs charge and the current through it falls away. Damp or dirty insulation leaks so freely that this effect is swamped, and the reading levels off almost at once.
For class F insulation a PI of 2 or more is recommended. Because both readings are taken at the same winding temperature, the PI is far less affected by temperature than a single reading. It is used when an IR value is suspect, and at surveys.