Insulation testing

How a megger tests insulation at high DC voltage, what reading is good enough, and why the polarisation index can catch a damp winding that a spot test passes.

Power distribution, page 6 of 103 min readUpdated 20 November 2026All 10 pages

An insulation resistance test is one of the best guides to the health of a motor, a cable or a switchboard. It is also one of the jobs an ETO does most. A megger pushes a high DC voltage across the insulation and measures how little current gets through.

An interactive insulation test loads here. It needs JavaScript; the sections below explain everything it shows.

What insulation resistance is

No insulation is perfect. Put a voltage across it and a very small current flows, some through the material and some across its surface. The insulation resistance, IR, is that voltage divided by that current. In healthy insulation it is huge, hundreds or thousands of megohms (MΩ). Moisture, dirt, oil, heat and age all bring it down.

Insulation fails gradually. A falling IR, recorded test after test, gives warning long before a winding burns out or a cable fails to earth.

The insulation tester

An insulation tester, often called a megger, is a resistance meter that tests at a high DC voltage, so that it stresses the insulation the way the working voltage does. A multimeter's few volts would tell you nothing.

EquipmentTest voltage
Ship's equipment rated 440 V AC500 V DC
High voltage equipment1,000 V or 5,000 V DC; 5,000 V for 6.6 kV
Making the test

The equipment must first be switched off, isolated, locked off and proved dead. Prove the tester itself first: with its two leads shorted together and the test button pressed, it should read zero.

On a three-phase motor, test each phase to earth, between the frame and each winding in turn, and then between the phases. A standard spot test is applied for one minute. Testing while the machine is still warm from running gives the most realistic reading, because insulation leaks more when it is hot.

What reading is good enough

For equipment up to 1,000 V, the minimum acceptable IR is usually 1 MΩ. For high voltage, a common rule is one megohm per kilovolt, plus one:

IRmin = (kV + 1) MΩ
kV = the equipment's voltage rating; for a 6.6 kV machine, 7.6 MΩ

These are minimums, not targets. Healthy insulation often reads up to a hundred times the minimum, and what matters most is how a reading compares with the last ones from the same machine.

Polarisation index

When a test voltage is applied, the reading does not settle at once. In good, dry insulation it keeps rising for minutes, as the insulating material slowly absorbs charge and the current through it falls away. Damp or dirty insulation leaks so freely that this effect is swamped, and the reading levels off almost at once.

PI = R10 ÷ R1
R10, R1 = the readings after 10 minutes and after 1 minute of the same test

For class F insulation a PI of 2 or more is recommended. Because both readings are taken at the same winding temperature, the PI is far less affected by temperature than a single reading. It is used when an IR value is suspect, and at surveys.

A good spot reading is not the whole story. A damp winding can read tens of megohms at one minute and still have a PI near 1. It passes the 1 MΩ test and fails the PI: dry it out before trusting it.
Check yourself
1. What test voltage is used on 440 V equipment?
500 V DC.
2. What is the minimum IR for a 3.3 kV motor by the (kV + 1) rule?
3.3 + 1 = 4.3 MΩ.
3. A winding reads 50 MΩ at one minute and 55 MΩ at ten. What does that tell you?
A PI of 55 ÷ 50 = 1.1: well under 2, so the insulation is probably damp or dirty, even though 50 MΩ is far above the minimum.

Going for your ETO CoC oral?

The full Insulation testing notes (T12), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014): insulation affected by humidity, temperature, dirt and age, and a minimum of at least 1 MΩ for voltages up to 1,000 V (p.8); circuit testing, the insulation tester, 500 V DC for 440 V equipment and 1,000 V or 5,000 V for HV, proving the tester, isolation first, testing between conductors and earth and between conductors (p.10); testing hot, and the value of a recorded trend (p.10); HV insulation: 5,000 V DC for 6.6 kV, one minute, correction to 40 °C, the (kV + 1) MΩ minimum, healthy readings up to 100 times the minimum, PI = R10 ÷ R1, 2 for class F, and PI's insensitivity to temperature (p.172).
  • Fernandez, E.A. Marine Electrical Technology: cable testing (14.7, p.566).
  • Elec-Buddy notes: T12 Cables and Earthing, T22 Maintenance (insulation testing).
  • The lab tests a 440 V motor winding at 500 V DC. Its insulation is modelled as a steady leakage resistance with an absorption current that dies away over the test; the three windings' values are illustrative, chosen to give a PI of about 3, about 1.1, and a reading under 1 MΩ. An automated test checks its figures against the page.