Earthing systems

Why most 440 V ship systems are insulated, what an earth fault does and does not do, earthed HV systems with a neutral earthing resistor, and equipment earthing.

Power distribution, page 5 of 103 min readUpdated 4 November 2026All 10 pages

"Earth" on a ship is the hull. A steel ship sits in sea water, and its hull is the earth everything is measured against. How the electrical system is connected to it, or not, decides what happens when a cable's insulation fails.

Interactive earth lamps on an insulated system loads here. It needs JavaScript; the sections below explain everything it shows.

The insulated system

Most ships' 440 V systems are insulated: no part of the supply is deliberately connected to the hull. If one phase develops a fault to earth, there is no complete path for a fault current. Only a small current flows, through the capacitance between the two healthy lines' cables and the hull, far too small to trip anything, so the equipment carries on working.

So a pump or the steering gear keeps going despite a first fault. But the fault must be found and cleared, because a second earth fault on another phase is a short circuit through the hull.

On board: earth fault lamps or an insulation monitor on the switchboard show when insulation has dropped. Finding the faulty circuit, by switching feeders off one at a time where it is safe, is a regular ETO job.

Earth lamps are the simplest indication. Three lamps are joined from the three lines to the hull through a common point. With no fault each has the phase voltage across it, 254 V on a 440 V system, and they glow equally and dimly. A solid earth fault on one line puts the hull at that line's voltage: its lamp goes dark, and the other two have the full line voltage across them and burn brightly. A fault of high resistance moves them only a little, so an insulation monitor, which reads the resistance to earth directly, gives a much earlier warning.

The earthed system

In an earthed system, the star point of the generator or transformer is connected to the hull. An earth fault then makes a fault current flow, and the protection trips the faulty circuit at once. On ships' high voltage systems the star point is usually earthed through a neutral earthing resistor, which limits that fault current to a safe value while still letting the protection see it.

Equipment earthing

Separate from how the supply is connected, every metal casing of electrical equipment, motor frames, panels and light fittings, is bonded to the hull. If a live wire touches the casing, the casing stays at hull potential instead of becoming live, so no one touching it gets a shock.

Insulated and earthed systems compared
InsulatedEarthed
First earth faultNo trip; alarm onlyTrips the faulty circuit
Main advantageSupply keeps goingFault found and cleared at once
On boardMost 440 V and 220 V systemsMost high voltage systems, through a resistor
Check yourself
1. Why does a first earth fault not trip an insulated system?
There is no complete path for fault current, since no part of the supply is connected to the hull.
2. Why must that first fault still be cleared quickly?
A second fault on another phase would be a short circuit through the hull.
3. What does a neutral earthing resistor do?
It limits the earth fault current on an earthed HV system while still letting the protection detect it.

Going for your ETO CoC oral?

The full Earthing systems notes (T12), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Fernandez, E.A. Marine Electrical Technology, chapter 5, Isolated and Earthed Neutral Systems (from p.137).
  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), chapter 2, distribution: insulated and earthed systems (p.22); equipment carrying on with a single earth fault, and a second fault on another line making a short circuit (p.24); earth indication lamps, the earth fault monitor on the main and emergency switchboards, and neutral earthing through a resistor on HV systems (p.25).
  • Elec-Buddy notes: T12 Cables and Earthing (the insulated neutral, earth fault finding), T02 High Voltage (the neutral earthing resistor).
  • The lab joins three earth lamps, taken as 60 W at 440 V, from the three lines of an insulated 440 V system to the hull, and finds the hull's voltage with Kirchhoff's current law (Wadhwa, chapter i, i.9). The lamp rating is illustrative. An automated test checks its figures against the page.