Electrical safety

What a shock current does to the body, why the body's resistance matters, what an RCD protects against and what it cannot, and safe isolation.

Power distribution, page 7 of 103 min readUpdated 20 November 2026All 10 pages

It is the current through the body that injures, not the voltage on its own. The voltage drives the current, the body's resistance limits it, and the path it takes through the body decides how much harm it does. Knowing how that works is what makes the safety rules make sense.

An interactive shock and RCD lab loads here. It needs JavaScript; the sections below explain everything it shows.

What the current does

An alternating current through the body is felt at about 1 mA. Above a few milliamps it hurts, and at 10 to 20 mA the muscles clamp, so a hand gripping a live part cannot let go. Higher still, the heart's rhythm can be thrown into ventricular fibrillation, a useless flutter, and at about 100 mA through the trunk that is likely to be fatal if it lasts a second or more.

CurrentEffect
1 mAFelt
5 mAThe upper limit of the harmless range
10 to 20 mALet-go threshold: the victim cannot let go
30 to 40 mASustained muscle contraction and cramp
50 to 70 mAExtreme pain, fainting, possible ventricular fibrillation
100 mAVentricular fibrillation and death, through the trunk

A current as low as 15 mA AC can be fatal, and people have died from voltages as low as 30 V.

The body's resistance

How much current flows depends on the body's resistance, and that is not fixed. Typical dry, full-contact resistance is about 5,000 Ω at 25 V, falling to about 2,000 Ω at 250 V: the resistance itself falls as the voltage rises. Wet skin brings it down to as little as 1,000 Ω.

I = V ÷ Rbody
220 V across about 2,000 Ω of dry skin drives about 110 mA: enough to kill

That is why control and alarm circuits on board run at 24 V, and why damp spaces, sweat and wet hands make every voltage more dangerous.

What an RCD protects against, and what it cannot

A residual current device compares the current going out on the live conductor with the current coming back. In a healthy circuit they are equal. If some current leaks to earth, through a person touching a live part and the hull, the two no longer balance, and the RCD trips. RCDs used for protecting people trip at a leak of 30 mA.

An RCD cannot see a shock between two lines. Touch two conductors of the same circuit, hand to hand, and the current goes out on one and back on the other. They still balance, and the RCD does nothing. It is a second line of defence. Isolating the supply is the first.
Safe isolation

Before working on any equipment: switch it off, isolate it, lock the isolator off and keep the key, and prove it dead with an approved voltage tester. On high voltage equipment it is also earthed before anyone touches it.

If someone is receiving a shock, switch off the current first. Do not touch them while they are still in contact with the supply.

Check yourself
1. Which does the harm: voltage or current?
The current through the body; the voltage drives it.
2. A person with wet hands, 1,000 Ω, touches 220 V. What current flows?
220 ÷ 1,000 = 220 mA: well into the fatal range.
3. Why will an RCD not protect someone touching two lines of the same circuit?
The current goes out on one line and back on the other, so the two still balance; the RCD only detects current leaking to earth.

Going for your ETO CoC oral?

The full Electrical safety notes (T12), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Fernandez, E.A. Marine Electrical Technology, chapter 2, electrical safety: the effects of shock depend on the current, the body's resistance and the contact (p.64); body resistance about 5,000 Ω dry at 25 V and 2,000 Ω at 250 V, 1,000 Ω wet hand to hand, deaths at voltages as low as 30 V, 15 mA AC possibly fatal and 100 mA fatal if it lasts a second or more (p.65); Table 2.3, the effects of shock current from 1 mA to over 5 A (p.66); switching off the current first in an electric shock (p.67); the residual current circuit breaker (11.8.1, p.424).
  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014): isolate and lock off before testing (p.10); HV equipment isolated, proved dead with an approved tester and earthed before work (p.172).
  • IEC 60364-4-41, protection against electric shock: additional protection by residual current devices with a rated residual operating current not exceeding 30 mA.
  • Elec-Buddy notes: T12 Cables and Earthing, T02 High Voltage (permit to work and earthing down).
  • The lab takes body resistance from Fernandez's figures, drawn as a straight line between 25 V and 250 V on log scales, and his Table 2.3 for the effects. The RCD trips at 30 mA; its 40 ms trip time is illustrative. An automated test checks its figures against the page.