An alternating current through the body is felt at about 1 mA. Above a few milliamps it hurts, and at 10 to 20 mA the muscles clamp, so a hand gripping a live part cannot let go. Higher still, the heart's rhythm can be thrown into ventricular fibrillation, a useless flutter, and at about 100 mA through the trunk that is likely to be fatal if it lasts a second or more.
| Current | Effect |
|---|---|
| 1 mA | Felt |
| 5 mA | The upper limit of the harmless range |
| 10 to 20 mA | Let-go threshold: the victim cannot let go |
| 30 to 40 mA | Sustained muscle contraction and cramp |
| 50 to 70 mA | Extreme pain, fainting, possible ventricular fibrillation |
| 100 mA | Ventricular fibrillation and death, through the trunk |
A current as low as 15 mA AC can be fatal, and people have died from voltages as low as 30 V.
How much current flows depends on the body's resistance, and that is not fixed. Typical dry, full-contact resistance is about 5,000 Ω at 25 V, falling to about 2,000 Ω at 250 V: the resistance itself falls as the voltage rises. Wet skin brings it down to as little as 1,000 Ω.
That is why control and alarm circuits on board run at 24 V, and why damp spaces, sweat and wet hands make every voltage more dangerous.
A residual current device compares the current going out on the live conductor with the current coming back. In a healthy circuit they are equal. If some current leaks to earth, through a person touching a live part and the hull, the two no longer balance, and the RCD trips. RCDs used for protecting people trip at a leak of 30 mA.
Before working on any equipment: switch it off, isolate it, lock the isolator off and keep the key, and prove it dead with an approved voltage tester. On high voltage equipment it is also earthed before anyone touches it.
If someone is receiving a shock, switch off the current first. Do not touch them while they are still in contact with the supply.