Cables

The layers of a marine cable, flame retardant and fire resistant cables, low smoke halogen free sheaths, how a cable is sized, and how it is installed.

Power distribution, page 8 of 103 min readUpdated 4 November 2026All 10 pages

A ship has hundreds of kilometres of cable. Marine cable is built in layers, each with its own job, and chosen for the current it carries, the voltage it must stand, and what it has to survive: heat, oil, vibration, sea air and fire.

An interactive cable sizing lab loads here. It needs JavaScript; the sections below explain everything it shows.

Cable construction
LayerIts job
ConductorCopper, made of many fine strands so the cable flexes with vibration without cracking.
InsulationKeeps each conductor apart from the others and from earth. Usually EPR or XLPE, which stand heat well.
Inner sheathBinds the cores together and bed for the armour.
Armour or braidA braid of wire that protects the cable mechanically, and is earthed. In signal cables a screen keeps out electrical noise.
Outer sheathResists oil, water and sunlight. Usually low smoke and halogen free.
Fire performance
  • Flame retardant cables do not spread a fire along their length. Most cables on board are this kind.
  • Fire resistant cables keep working while they burn, for a set time, because a mica tape round the conductors stays intact as an insulator when the plastic burns away. They are used for circuits that must work in a fire, such as emergency lighting, fire alarms and emergency fire pumps.
  • Low smoke, halogen free sheaths give off little smoke and no corrosive gas when they burn, so people can see to escape.
Cable sizing

A cable is sized for two things. It must carry its current without overheating, and the bigger the current, the thicker the conductor. And its voltage drop over its length must stay small enough for the load at the far end to work properly. A long run may need a larger cable than its current alone would suggest.

Both tests come from rating tables. A cable's current rating is the current at which its conductor settles at about 80 °C in a 45 °C engine room, the conductor temperature the table is built on; the temperature rise goes with the square of the current. In a hotter space, or bunched with other cables, the rating has to be reduced. The voltage drop from the switchboard to the load must not exceed 6%, and in practice it is usually about 2%.

Vdrop = (mV per A per m) × I × L ÷ 1000
the mV figure comes from the cable table; for 4 mm² three-core on AC it is 10 mV

Example: 30 A over 60 m of 6 mm² cable, at 6.7 mV per amp per metre: 6.7 × 30 × 60 ÷ 1000 = 12 V, or 2.7% of 440 V. The same load 200 m away loses 40 V, over 9%, and needs a bigger cable even though 6 mm², rated 34 A, carries the current comfortably.

Installation

Cables run on trays and in trunking, clipped at intervals. Where they pass through a watertight bulkhead or deck, they go through a sealed transit or gland so the bulkhead stays watertight and fire-tight. At the equipment, a cable gland holds the cable, seals it and earths its armour.

Check yourself
1. Why are marine cable conductors stranded?
So the cable can flex with vibration without the conductor cracking.
2. Which cables must keep working in a fire?
Fire resistant cables, on circuits such as emergency lighting and fire alarms.
3. Why might a long cable need a bigger size than its current needs?
To keep the voltage drop small enough for the load at the far end.

Going for your ETO CoC oral?

The full Cables notes (T12), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Fernandez, E.A. Marine Electrical Technology, chapter 14, cables: current rating and voltage drop (14.4, p.561), the 6% limit on voltage drop and about 2% in practice (p.561), Table 14.1 of ratings and voltage drop (p.562), and the 80 °C conductor temperature at rated current in a 45 °C ambient, a 35 °C rise, with rating factors for other air temperatures under the table (14.4, p.561-562).
  • IEC 60331: fire resistant cables, which keep working in a fire for a set time; marine cables are commonly certified for 90 minutes.
  • Elec-Buddy notes: T12 Cables (cable layers, EPR, XLPE and LSZH, flame retardant and fire resistant cable, sizing, transits).
  • The lab uses Fernandez's Table 14.1 (p.562): current ratings and voltage drop for three and four core cable on AC, from 1.5 to 25 mm². The 16 mm² voltage drop is unclear in the print and is taken as 2.3 mV per amp per metre, since every other row's AC figure is 0.866 times its DC one (2.7 × 0.866). An automated test checks its figures against the table and the page.
  • Where sources disagree: Fernandez gives two ambients for the same 80 °C. On p.552 it is 40 °C above a 40 °C ambient; in the current rating section (p.561) it is a 45 °C ambient, a 35 °C rise, and Table 14.1's rating factor is 1.00 at 45 °C. The page and the lab follow the table.