| Layer | Its job |
|---|---|
| Conductor | Copper, made of many fine strands so the cable flexes with vibration without cracking. |
| Insulation | Keeps each conductor apart from the others and from earth. Usually EPR or XLPE, which stand heat well. |
| Inner sheath | Binds the cores together and bed for the armour. |
| Armour or braid | A braid of wire that protects the cable mechanically, and is earthed. In signal cables a screen keeps out electrical noise. |
| Outer sheath | Resists oil, water and sunlight. Usually low smoke and halogen free. |
- Flame retardant cables do not spread a fire along their length. Most cables on board are this kind.
- Fire resistant cables keep working while they burn, for a set time, because a mica tape round the conductors stays intact as an insulator when the plastic burns away. They are used for circuits that must work in a fire, such as emergency lighting, fire alarms and emergency fire pumps.
- Low smoke, halogen free sheaths give off little smoke and no corrosive gas when they burn, so people can see to escape.
A cable is sized for two things. It must carry its current without overheating, and the bigger the current, the thicker the conductor. And its voltage drop over its length must stay small enough for the load at the far end to work properly. A long run may need a larger cable than its current alone would suggest.
Both tests come from rating tables. A cable's current rating is the current at which its conductor settles at about 80 °C in a 45 °C engine room, the conductor temperature the table is built on; the temperature rise goes with the square of the current. In a hotter space, or bunched with other cables, the rating has to be reduced. The voltage drop from the switchboard to the load must not exceed 6%, and in practice it is usually about 2%.
Example: 30 A over 60 m of 6 mm² cable, at 6.7 mV per amp per metre: 6.7 × 30 × 60 ÷ 1000 = 12 V, or 2.7% of 440 V. The same load 200 m away loses 40 V, over 9%, and needs a bigger cable even though 6 mm², rated 34 A, carries the current comfortably.
Cables run on trays and in trunking, clipped at intervals. Where they pass through a watertight bulkhead or deck, they go through a sealed transit or gland so the bulkhead stays watertight and fire-tight. At the equipment, a cable gland holds the cable, seals it and earths its armour.