Circuit breakers

What a breaker does, how the arc is broken, the types on board, what makes them trip, and an ACB's connected, test and isolated positions.

Power distribution, page 2 of 102 min readUpdated 4 November 2026All 10 pages

A circuit breaker is a switch that can open itself. It carries the load current all day, and when something goes wrong, an overload or a short circuit, it trips open automatically and stops the fault. Unlike a fuse, it can then be reset and used again.

An interactive draw-out air circuit breaker loads here. It needs JavaScript; the sections below explain everything it shows.

Arc interruption

When contacts carrying a large current part, the current does not stop at once: it jumps the gap as an arc, a column of very hot, conducting gas. Breaking a circuit really means putting that arc out. On AC the current passes through zero twice every cycle, and a breaker is designed so the arc goes out at a zero and cannot strike again. How it does that is what separates the types.

Types of circuit breaker
TypePuts the arc outUsed for
ACB, air circuit breakerDrives the arc up into an arc chute of plates that split and cool itGenerators, the bus-tie, the largest feeders
MCCB, moulded caseA small arc chute inside a sealed moulded caseFeeders to motors and distribution boards
MCB, miniatureThe same idea, smallerFinal circuits: lighting and small power
VCB, vacuumContacts in a vacuum, where the arc has nothing to keep it goingHigh voltage systems
SF6 breakerContacts in sulphur hexafluoride gas, which quenches the arcHigh voltage systems
Trip units
  • Overload: a current a little above rating for some time. The trip waits, longer for a small overload and shorter for a big one.
  • Short circuit: a very large current. The trip acts at once.
  • Undervoltage: on a generator breaker, the undervoltage release opens it when the voltage is lost, and stops it being closed onto a dead generator.
  • On generator ACBs, protection relays can also trip it, for example on reverse power.

As a guide, a generator breaker's overcurrent trip is typically set at about 150% of rated current with a delay of about 20 seconds, long enough for a motor to start or a feeder fault to be cleared further down. Its short-circuit trip is close to instantaneous, under 50 ms. The breakers further down, nearer the loads, are set lower and faster, so a fault on a feeder is cleared by that feeder's own breaker and the generator stays on the board. This grading is called discrimination.

Draw-out positions of an ACB

Large ACBs are draw-out: the breaker sits on rails and can be racked between three positions.

PositionMain contactsControl circuit
Connected (service)Connected to the busbarsConnected
TestDisconnectedConnected, so it can be closed and tripped safely
Isolated (disconnected)DisconnectedDisconnected
Check yourself
1. What is the hard part of breaking a large current?
Putting out the arc that forms between the opening contacts.
2. Which breaker type would you find on a generator?
An ACB, or a VCB or SF6 breaker on a high voltage system.
3. In the test position, can an ACB be closed?
Yes: its control circuit is connected, but its main contacts are clear of the busbars.

Going for your ETO CoC oral?

The full Circuit breakers notes (T04), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), chapter 3, generators and main circuit breakers (from p.49): ACB construction, arc chutes, trip units and the undervoltage release.
  • Fernandez, E.A. Marine Electrical Technology: the arc drawn into the chute and split and cooled by its plates (p.409-413); chapter 13, fault protection devices (from p.489).
  • Elec-Buddy notes: T04 Switchboards (ACB positions, MCCB and MCB), T02 High Voltage (vacuum and SF6 breakers).
  • The lab is a generator breaker rated 1,000 A. Its overcurrent element picks up at 150% and trips after 20 s, the generator setting Hall gives (p.20); its instantaneous element trips in a few hundredths of a second, as Hall describes (under 50 ms, p.40), and is set here at 5 times rated, an illustrative figure. An automated test checks its figures. Discrimination, with the devices nearest the load set lowest and fastest: Hall p.38-39, Figure 2.28.
  • ABB, Technical Application Paper No.12, Generalities on naval systems and installations on board, section 7.2 (p.26): a generator's short-circuit protection trips the breaker instantaneously at a current below the generator's steady short-circuit current; its overload protection acts between 10 and 50% over rated current, within 2 minutes at 1.5 times rated; selectivity between incoming and outgoing breakers is required.