When contacts carrying a large current part, the current does not stop at once: it jumps the gap as an arc, a column of very hot, conducting gas. Breaking a circuit really means putting that arc out. On AC the current passes through zero twice every cycle, and a breaker is designed so the arc goes out at a zero and cannot strike again. How it does that is what separates the types.
| Type | Puts the arc out | Used for |
|---|---|---|
| ACB, air circuit breaker | Drives the arc up into an arc chute of plates that split and cool it | Generators, the bus-tie, the largest feeders |
| MCCB, moulded case | A small arc chute inside a sealed moulded case | Feeders to motors and distribution boards |
| MCB, miniature | The same idea, smaller | Final circuits: lighting and small power |
| VCB, vacuum | Contacts in a vacuum, where the arc has nothing to keep it going | High voltage systems |
| SF6 breaker | Contacts in sulphur hexafluoride gas, which quenches the arc | High voltage systems |
- Overload: a current a little above rating for some time. The trip waits, longer for a small overload and shorter for a big one.
- Short circuit: a very large current. The trip acts at once.
- Undervoltage: on a generator breaker, the undervoltage release opens it when the voltage is lost, and stops it being closed onto a dead generator.
- On generator ACBs, protection relays can also trip it, for example on reverse power.
As a guide, a generator breaker's overcurrent trip is typically set at about 150% of rated current with a delay of about 20 seconds, long enough for a motor to start or a feeder fault to be cleared further down. Its short-circuit trip is close to instantaneous, under 50 ms. The breakers further down, nearer the loads, are set lower and faster, so a fault on a feeder is cleared by that feeder's own breaker and the generator stays on the board. This grading is called discrimination.
Large ACBs are draw-out: the breaker sits on rails and can be racked between three positions.
| Position | Main contacts | Control circuit |
|---|---|---|
| Connected (service) | Connected to the busbars | Connected |
| Test | Disconnected | Connected, so it can be closed and tripped safely |
| Isolated (disconnected) | Disconnected | Disconnected |