The primary winding is fed with AC. Its changing current sets up a changing magnetic flux in the core, which is made of thin laminated steel. That same flux passes through the secondary winding and induces a voltage in it: mutual induction. Because it relies on the flux changing, a transformer works on AC only.
A ship's three-phase lighting transformer is usually a core type: the windings are wound round the limbs of the core, one limb for each phase, with yokes joining the limbs top and bottom. The core is built of thin steel laminations, about 0.5 mm, to keep the eddy currents small. On each limb the low voltage winding sits next to the core and the high voltage winding round the outside. In the lab, the middle limb's windings are cut away to show this.
The lab's unit is a dry type, as most ships' lighting transformers are: copper windings varnished by vacuum pressure impregnation, cooled by air flowing up through the windings, in a ventilated steel enclosure. There is no oil to leak or catch fire. Turn the lab to Names to find the parts.
Each turn of wire on the core gets the same voltage, so the voltage of each winding is in proportion to its number of turns. Fewer turns on the secondary steps the voltage down; more steps it up. The power in and out is nearly the same, so as the voltage goes down the current goes up in the same ratio.
Example: a 440/220 V lighting transformer has twice as many turns on its primary as on its secondary. If the 220 V side supplies 40 A, the 440 V side draws about 20 A.
With no moving parts and only these two losses, a transformer is very efficient, often well over 95%.
The two losses behave differently as load changes. The iron loss is fixed by the flux, so it is the same at any load. The copper loss rises with the square of the current. Efficiency is greatest at the load where the two are equal. For the lab's transformer, with 570 W of iron loss and 3,512 W of copper loss at full load, that is at about 40% load, where it reaches 98.6%; at full load it is still 98%. Find it in the lab's chart.
The secondary voltage falls a little as load comes on, because the load current flows through the windings' own resistance and reactance. This fall is the voltage regulation, roughly r cos φ + x sin φ in per unit, where r and x are the transformer's resistance and reactance. For the lab's unit it is under 2% at full load.
To set the secondary voltage, the HV winding has taps: here 450, 440 and 430 V, chosen by moving a link. More primary turns give a lower secondary voltage. These are off-load taps: the transformer must be switched off and isolated before the link is moved. The lab will not let you change the tap while it is on.
Even with no load, the primary draws a small magnetising current, about 5% of rated for the lab's unit, to set up the flux. At the instant of switching on it can draw a much larger inrush current for a moment, several thousand amps for a 200 kVA unit, while the core's flux settles.
| Kind | What it does |
|---|---|
| Power transformer | Steps HV down to 440 V on ships with a high voltage system. |
| Lighting transformer | Steps 440 V down to 220 V for lighting and small power. |
| Isolation transformer | Same voltage in and out, but with no connection between the two sides, so the secondary circuit is separated from the main system. |
| Current transformer (CT) | Steps a large current down to a small one, often 5 A or 1 A, for meters and protection relays. |
| Voltage transformer (VT or PT) | Steps a high voltage down for meters and relays. |