Transformer

Mutual induction, the turns ratio, core-type construction, copper and iron losses and where efficiency peaks, taps and regulation, and the transformers on a ship, with a ship's lighting transformer you can switch on and load.

Machines, page 6 of 65 min readUpdated 19 November 2026All 6 pages

A transformer changes the voltage of AC with no moving parts. Two coils share one iron core, and power passes from one to the other through the magnetic field alone. On a ship it is how 440 V becomes 220 V for the lighting, and how high voltage becomes 440 V.

An interactive ship's lighting transformer loads here. It needs JavaScript; the sections below explain everything it shows.

Principle of operation

The primary winding is fed with AC. Its changing current sets up a changing magnetic flux in the core, which is made of thin laminated steel. That same flux passes through the secondary winding and induces a voltage in it: mutual induction. Because it relies on the flux changing, a transformer works on AC only.

Construction

A ship's three-phase lighting transformer is usually a core type: the windings are wound round the limbs of the core, one limb for each phase, with yokes joining the limbs top and bottom. The core is built of thin steel laminations, about 0.5 mm, to keep the eddy currents small. On each limb the low voltage winding sits next to the core and the high voltage winding round the outside. In the lab, the middle limb's windings are cut away to show this.

The lab's unit is a dry type, as most ships' lighting transformers are: copper windings varnished by vacuum pressure impregnation, cooled by air flowing up through the windings, in a ventilated steel enclosure. There is no oil to leak or catch fire. Turn the lab to Names to find the parts.

The turns ratio

Each turn of wire on the core gets the same voltage, so the voltage of each winding is in proportion to its number of turns. Fewer turns on the secondary steps the voltage down; more steps it up. The power in and out is nearly the same, so as the voltage goes down the current goes up in the same ratio.

V1 ÷ V2 = N1 ÷ N2 = I2 ÷ I1
V = voltage, N = turns, I = current; 1 = primary, 2 = secondary

Example: a 440/220 V lighting transformer has twice as many turns on its primary as on its secondary. If the 220 V side supplies 40 A, the 440 V side draws about 20 A.

Losses and efficiency
Copper loss
Heat in the windings from their resistance, I²R. It rises with the load.
Iron loss
Hysteresis and eddy currents in the core. It is there whenever the transformer is energised, loaded or not.

With no moving parts and only these two losses, a transformer is very efficient, often well over 95%.

The two losses behave differently as load changes. The iron loss is fixed by the flux, so it is the same at any load. The copper loss rises with the square of the current. Efficiency is greatest at the load where the two are equal. For the lab's transformer, with 570 W of iron loss and 3,512 W of copper loss at full load, that is at about 40% load, where it reaches 98.6%; at full load it is still 98%. Find it in the lab's chart.

Taps and voltage regulation

The secondary voltage falls a little as load comes on, because the load current flows through the windings' own resistance and reactance. This fall is the voltage regulation, roughly r cos φ + x sin φ in per unit, where r and x are the transformer's resistance and reactance. For the lab's unit it is under 2% at full load.

To set the secondary voltage, the HV winding has taps: here 450, 440 and 430 V, chosen by moving a link. More primary turns give a lower secondary voltage. These are off-load taps: the transformer must be switched off and isolated before the link is moved. The lab will not let you change the tap while it is on.

Even with no load, the primary draws a small magnetising current, about 5% of rated for the lab's unit, to set up the flux. At the instant of switching on it can draw a much larger inrush current for a moment, several thousand amps for a 200 kVA unit, while the core's flux settles.

Transformers on board
KindWhat it does
Power transformerSteps HV down to 440 V on ships with a high voltage system.
Lighting transformerSteps 440 V down to 220 V for lighting and small power.
Isolation transformerSame voltage in and out, but with no connection between the two sides, so the secondary circuit is separated from the main system.
Current transformer (CT)Steps a large current down to a small one, often 5 A or 1 A, for meters and protection relays.
Voltage transformer (VT or PT)Steps a high voltage down for meters and relays.
Never open the secondary of a CT while current flows in its primary. With nothing to oppose it, the core's flux rises hugely and a dangerously high voltage appears across the open terminals. Short the secondary first, then disconnect the meter.
Check yourself
1. A transformer has 400 turns on its primary and 200 on its secondary, with 440 V in. What comes out?
220 V, half the voltage for half the turns.
2. Why does a transformer not work on DC?
DC gives a steady flux, and only a changing flux induces a voltage in the secondary.
3. At what load is a transformer most efficient?
Where its copper loss equals its iron loss; about 40% load for the lab's unit.
4. A lighting transformer's secondary reads a little high. You move its tap from 440 V to 450 V. What must you do first, and what happens?
Switch it off and isolate it (off-load taps). More primary turns, so the secondary voltage falls.
5. Why must a CT secondary never be left open?
The core flux rises and a dangerously high voltage appears across the open terminals.

Going for your ETO CoC oral?

The full Transformer notes (T05), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Wadhwa, C.L. Basic Electrical Engineering, chapter 5, transformers: construction (5.2, p.204), the emf equation and turns ratio (5.3, p.205), losses (5.10, p.221), efficiency (5.11, p.222), the autotransformer (5.14, p.232); mutual inductance (ii.7, p.36).
  • Wadhwa, more detail: core type and shell type, with the windings round the limbs of a core type (5.2, p.204); the low voltage winding placed near the core and the high voltage outside it (5.2, p.204); voltage regulation in per unit, r cos φ ± x sin φ (p.220); laminations about 0.5 mm against eddy currents (p.222); maximum efficiency where copper loss equals iron loss (p.224).
  • Fernandez, E.A. Marine Electrical Technology: transformers on board are generally air-cooled dry types (16.2, p.601); distribution transformers of 500 kVA or less are dry, air-cooled and drip-proof, in sheet steel enclosures (p.613). Hall, p.31: ship's transformers are generally air cooled, in sheet steel enclosures often next to the main switchboard.
  • KOC Electric, specification for L.V. transformers (dry type, IEC 60076-11; cited by maker), technical data sheet 7.1 and outline drawing for the 200 kVA, 440 / 230 V, Dd0 main lighting transformer: VPI copper windings, natural air cooling, off-load taps F450 - R440 - 430 V, no-load current 5.0%, impedance 4.0% (resistance 1.7%, reactance 3.62%), no-load loss 570 W, load loss 3,512 W, in-rush current 3.02 kA, rated currents 262.4 A and 502.0 A; the lab's unit is built to this sheet and drawing.
  • The lab's figures come from that data sheet; the regulation, efficiency and the peak at about 40% load are worked out from it at unity power factor, as the maker's figures are given. An automated test checks them.
  • Where sources disagree: Wadhwa (p.224) says power transformers are normally designed to be most efficient at 75 to 85% of full load. The lab's lighting transformer peaks at about 40%, because its maker's iron loss is small next to its full-load copper loss. Where the peak falls depends on the design; the rule that it comes where the two losses are equal does not.
  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), chapter 2, distribution (from p.19): transformers supplying the lighting and low voltage systems.
  • Elec-Buddy notes: T05 Transformers (lighting, isolation, current and voltage transformers; the CT open-circuit danger).