Wind a coil of wire round an iron core and pass a current through it, and the iron becomes a magnet. Stop the current and most of the magnetism goes. Increase the current and the magnet gets stronger. That is an electromagnet, and the rotor of every ship's alternator is one.
Why not use a permanent magnet? Because then nobody could adjust it. With an electromagnet, the current in the rotor winding works like a dimmer on a light: turn it up, the magnetic field, called the flux (Φ), gets stronger. Feeding that current is called excitation, and you will meet it in every section of T01.
Push a magnet into a coil and a meter on the coil kicks. Hold it still and the meter reads nothing. Pull it out and the meter kicks the other way. Faraday found this: a voltage (EMF) appears only while the magnetism through the coil is changing.
Think of driving through rain. Parked, few drops hit the windscreen. Drive faster and more drops hit every second. Drive into heavier rain and more hit again. The voltage behaves the same way: it grows with how strong the field is and with how fast it sweeps past the coil.
The rain picture stops working in one place: rain does not push back on the car. Induced current does. Lenz showed that the current produced always opposes the movement that made it. So when the ship's load goes up, the alternator gets harder to turn, and the engine driving it has to burn more fuel to keep up. Electrical load becomes load on the engine.
As the rotor turns, a north pole sweeps past a stator coil, then a south pole. North pushes the current one way, south pushes it back. The voltage swings up, through zero, down, and back: one full swing is one cycle. A pair of poles (one north, one south) passing a coil gives one cycle.
So the frequency is just "pole pairs that pass per second". Work it out for a 4-pole rotor, which has 2 pairs, turning at 1800 rev/min:
- 1800 rev/min ÷ 60 = 30 revolutions per second.
- Each revolution brings 2 pole pairs past the coil, so 2 cycles per revolution.
- 30 × 2 = 60 cycles per second = 60 Hz.
You will find it at the top of T01. The 120 is nothing mysterious: it is 60 (seconds in a minute) times 2 (poles in a pair). It also tells you why frequency is held by keeping the engine at a steady speed.
An AC voltage is always changing, so which number do we put on the nameplate? We use the rms value: the steady DC voltage that would heat a resistor exactly as much. So a 440 V AC supply and a 440 V DC supply boil a kettle in the same time.
The peak is higher. For a sine wave it is 1.414 (that is √2) times the rms value:
Put three separate coils in the stator, spaced evenly round the bore, 120° apart. The rotor field reaches each one a third of a turn after the last, so you get three identical voltages, each a third of a cycle behind the one before. A single-cylinder engine gives one push per cycle and shakes; a multi-cylinder engine spreads its firing round the crank and runs smoothly. Three phases do the same for electrical power.
Join one end of each coil together (the star point) and take the line conductors from the other ends. The voltage between two lines is not twice the phase voltage, because the two phase voltages are 120° apart, not in line. Work it through:
- Line voltage is the difference between two phase voltages of equal size V, 120° apart.
- Drawn as arrows, that difference is the third side of a triangle whose other two sides are V and the angle between them is 120°.
- Its length works out to 2 × V × sin 60° = 2 × V × 0.866 = 1.732 × V, and 1.732 is √3.
Picture a horse on a canal towpath pulling a barge with a rope. The rope runs at an angle, so only part of the horse's pull moves the barge along the canal. The rest pulls sideways, toward the bank, and does no useful work, but the rope still has to carry it.
| On the canal | In the switchboard | Unit |
|---|---|---|
| Pull along the canal, moving the barge | Active (true) power: does the work | kW |
| Sideways pull toward the bank | Reactive power: magnetises motors and transformers, does no work | kVAr |
| Total tension in the rope | Apparent power: what the cables and windings must carry | kVA |
| Cosine of the rope's angle | Power factor, cos φ = kW ÷ kVA | 0 to 1 |
A ship's load is mostly motors, so the current lags the voltage. A typical figure is 0.8 lagging, which means the current is about 37° behind the voltage (cos 37° ≈ 0.8). The analogy breaks here: reactive power is not wasted the way the bank-ward pull is. Motors need it to build their magnetic fields; it just flows back and forth instead of doing work.
Try it with numbers. A 440 V generator is supplying 500 kW at 0.8 power factor:
- Apparent power: 500 kW ÷ 0.8 = 625 kVA.
- Current: P = √3 × V × I × cos φ, so I = 500,000 ÷ (1.732 × 440 × 0.8) = 500,000 ÷ 609.7 ≈ 820 A.
- At unity power factor the same 500 kW would need only 656 A. At 0.8 the current also carries a reactive part, 820 × 0.6 ≈ 492 A, at right angles to the working 656 A; the two combine as the sides of a right-angled triangle to make the 820 A the windings carry.
Put ideas 2 and 3 side by side and the whole job of running a generator falls out of them:
Why does the voltage need holding at all? When load current flows, some voltage is lost inside the alternator's own windings (current times the winding impedance). Start a big pump and the terminal voltage dips, typically by about 15%; the AVR then raises excitation to bring it back. A conventional exciter can take up to a second to do it. A static, compound-excited set reacts much faster.
The set in the lab is built to the maker drawings of a real marine emergency generating set: a 500 kW, 625 kVA, 450 V, 60 Hz brushless alternator with four poles at 1,800 rpm, driven by a V12 diesel through a disc coupling, with the radiator at the front and everything on one common bed. Switch the lab to Names and turn it round. Most marine generators are built the same way.
| Part | What it does |
|---|---|
| Stator | A laminated steel core with the three-phase winding in slots round its bore. Its six ends come out in the terminal box. This is where the output is induced. |
| Salient pole rotor | Poles that stand out from the hub, each with its field coil wound round it. This is the usual marine rotor, used at 1,800 rpm and below. Fast turbine-driven sets use a smooth cylindrical rotor with the winding in slots instead. |
| Exciter | A small AC generator at the non-drive end, the other way round from the main machine: its field is on the stator and its output winding on the rotor. The AVR feeds its stationary field. |
| Permanent magnet pilot exciter (PMG) | On many sets, a small generator with permanent magnets on the end of the shaft. It powers the AVR from the machine itself, independent of the main output, so excitation holds up even during a heavy dip or a short circuit. |
| Rotating diodes | Six silicon diodes on a wheel on the shaft, a three-phase bridge, turning the exciter's AC into DC for the main field. A varistor across the field protects them from voltage surges. |
| AVR | Senses the output voltage (and, on many sets, the current) and sets the exciter field to hold the voltage. |
Because the exciter's output is rectified on the rotor itself, no current has to pass through brushes or slip rings. That is what brushless means, and it removes the brush wear and carbon dust that older sets needed looking after. In the lab, the orange glow on the exciter and the rotor coils is the field current: watch it rise when the AVR has to work harder.
Put load on in the lab and the frequency does not stay exactly at 60 Hz. The engine slows a little, the governor adds fuel to stop it, and the set settles at a slightly lower speed. That small, deliberate fall in speed from no load to full load is the governor's droop.
Droop is there on purpose. Two generators in parallel run at the same frequency, and droop is what decides how they share the kW between them. Without it, neither would know how much of the load to take. To bring the frequency back to 60 Hz, the engineer raises the governor setting from the switchboard (the Raise and Lower buttons in the lab); on paralleled sets, raising one machine's setting while lowering the other's moves kW from one to the other. Autoload sharing equipment does the same thing automatically.
Start a large motor and it takes several times its running current at a very poor power factor. Most of that is reactive current, and it pulls the alternator's voltage down at once: a voltage dip. The field cannot change instantly, so for a moment nothing can stop it. Then the AVR forces the field up and brings the voltage back.
| What class rules expect | Limit |
|---|---|
| Dip when a sudden load at low power factor (0 to 0.4) is switched on | Not below 85% of rated voltage |
| Rise when that load is switched off | Not above 120% |
| Recovery | Back within 3% of rated voltage in 1.5 seconds |
| Recovery, emergency generator | Back within 4% in 5 seconds. This is the voltage settling after a load is switched on; the 45 seconds in SOLAS is a different rule, the time it has to start and take the load after a blackout. |
Try it in the lab with some load already on: start the 55 kW pump and the readings report the dip and how long the AVR took. Then take the AVR out (Manual) and do it again. With the field fixed by hand, the voltage falls further and stays low, and adding kVAr pulls it down steadily. That is why every ship's generator has an AVR, and why the field is only run by hand in an emergency.
The opposite happens when a big load comes off: the field is still set for the heavy load, so the voltage overshoots until the AVR brings the field back down. You can see a small overshoot in the lab just after the pump has run up.
| Word | What it means |
|---|---|
| Stator | The stationary outer part. In an alternator it carries the three-phase output windings. |
| Rotor | The rotating part, carrying the field winding (the electromagnet). |
| Armature | The winding in which the output voltage is induced. In a ship's alternator that is the stator. |
| Field winding / excitation | The rotor coil, and the DC current fed into it to make the magnetic field. |
| Exciter | A small generator on the same shaft that supplies the excitation current. |
| Brushless | An alternator whose exciter output is rectified by diodes on the rotor, so no brushes or slip rings carry the field current. |
| AVR | Automatic voltage regulator: adjusts excitation to hold the output voltage. |
| Prime mover / governor | The engine or turbine that turns the alternator, and the control that holds its speed. |
| Residual magnetism | The weak magnetism left in the rotor iron after shutdown. It gives a self-excited set enough voltage to start building up. |
| Synchronising / paralleling | Matching an incoming generator's voltage, frequency and phase to the busbar before closing its breaker. |
| Droop | A deliberate small fall in speed (or voltage) as load rises, so that parallel generators share load steadily. |
| IR test | Insulation resistance test with a megger, to check the windings' insulation. |
Answer each in your head before you open it. If all eight come easily, you are ready for the notes.
1. A 6-pole alternator must give 60 Hz. What speed must it run at?
2. Engine speed is steady, a large motor starts and the voltage dips. What brings it back?
3. The switchboard reads 440 V. What is the peak voltage the insulation sees?
4. On a 440 V star system, what is the voltage from a line to the star point?
5. Why is an alternator rated in kVA rather than kW?
6. A generator runs at 61.8 Hz on no load and 60 Hz on full load. What is its droop?
7. In a brushless alternator, how does the field current reach the rotor?
8. A big pump starts and the voltage dips. What do class rules expect of the AVR?
These links open the Alternator topic in the Elec-Buddy app. It is the free preview topic, so a free account is enough.
- Working Principle & Construction: ideas 1, 2 and 3, the frequency formula and its speed table.
- Excitation Systems and Brushless Alternator: idea 1, how the field current gets to the rotor.
- AVR: idea 7, holding the voltage as load changes.
- kVA vs kW, Numerical Example: idea 6, with a full worked example.
- Parallel Operation and Droop: ideas 6 and 7 with two generators sharing load.