DC machines

How a DC machine is built, what the commutator and interpoles do, back emf and starting, shunt, series and compound connections, speed control and the no-field trip, with a DC winch motor you can start and run yourself.

Machines, page 5 of 66 min readUpdated 19 November 2026All 6 pages

DC machines are rarer on ships now, replaced by induction motors with variable frequency drives. You will still meet them in older deck machinery and cranes, in some emergency and battery-powered equipment, and in every textbook, because they show the motor and generator principles most plainly.

An interactive DC motor loads here. It needs JavaScript; the sections below explain everything it shows.

Construction

The field is on the stator: poles with coils, fed with DC, giving a fixed magnetic field. The armature is the rotor: coils in a slotted iron core, connected to a commutator, a ring of copper segments, on which carbon brushes press. Turn the lab to Names to find each part.

PartWhat it does
YokeThe steel frame. It carries the magnetic flux from pole to pole, and the poles are bolted to it; you can see the bolt heads on the outside.
Main poles and field coilsElectromagnets in pairs, north and south alternately, set with thin shims to keep the air gap right. Each can carry a shunt coil of many fine turns and a series coil of a few heavy turns.
InterpolesSmaller poles midway between the main poles, with their coils in series with the armature. They correct the flux where the brushes commutate.
ArmatureA laminated core on the shaft with its coils in slots, each coil's ends joined to commutator segments.
Commutator and brushesCopper segments insulated from each other with mica; carbon brushes in holders on a rocker ring press on them and carry the current in and out.
The commutator

A coil turning in a fixed field has its voltage reverse every half turn. The commutator reverses the coil's connection to the brushes at just that moment. In a generator that turns the coil's alternating voltage into DC at the brushes; in a motor it reverses the current in each coil as it passes a pole, so the force on it always pushes the same way round.

Open the lab's Commutator view with the motor running. Each armature conductor glows orange on one side of a brush and blue on the other: its current reverses as its coil passes under the brush, midway between the poles. The pattern stays still while the armature turns through it.

The commutator and brushes are also the parts that wear. They need regular attention: brush length and spring pressure, a clean, evenly coloured commutator, and no sparking.

Armature reaction and interpoles

The armature current makes a field of its own, across the main field. It distorts the main flux, strengthening it at one tip of each pole and weakening it at the other, and shifts the neutral plane where the brushes should commutate. The coils being commutated then still have a voltage in them, and the brushes spark.

Three things counter it: pole tips shaped to carry a high flux density, compensating windings in the pole faces, and interpoles. Because the interpole coils carry the armature current, their correcting flux grows with the load, just as the distortion does. The brush position can also be adjusted slightly on the rocker for the least sparking.

In the lab, the interpole coils glow with the armature current. Push the current well past rated, or weaken the field hard, and the brushes start to spark.

Back emf and starting

A turning armature is also a generator, so it makes a voltage opposing the supply: the back emf. It is proportional to the speed and to the field's strength. Only the difference between the supply and the back emf drives current through the armature's small resistance.

Ia = (V − Eb) ÷ Ra
Ia = armature current, V = supply, Eb = back emf, Ra = armature resistance

At standstill there is no back emf, and only the armature's small resistance limits the current, so a DC motor is started with a resistance in series that is cut out step by step as it speeds up. The lab's chart V = Eb + IaR shows it: at the first stud almost all the supply is across the resistance; at full speed the back emf takes nearly all of it.

N ∝ (V − IaRa) ÷ Φ
N = speed, Φ = field flux. The speed rises with the voltage across the armature and falls as the field gets stronger
Field connections: shunt, series and compound
TypeField connectedHow it behaves
ShuntAcross the supply, in parallel with the armatureNearly steady speed as the load changes; reasonable starting torque
SeriesIn series with the armature, carrying the same currentVery high starting torque; speed rises sharply as load falls, so it must never run without load
CompoundBoth a shunt and a series winding, usually aiding each other (cumulative)Between the two: good starting torque and a steadier speed

Why the series motor runs away: its field is made by the armature current. Take the load off and the current falls, so the field falls, so the back emf per rpm falls, and the motor has to turn faster and faster to make enough back emf. Many series motors carry a small shunt field to stop this.

Speed control

A DC motor's speed is easy to control. That made DC the old choice for winches, cranes and lifts.

  • Below base speed: lower the voltage across the armature, or add resistance in its circuit. Less voltage left for back emf means a lower speed.
  • Above base speed: weaken the field with a rheostat in the shunt field. A weaker field gives less back emf per rpm, so the motor runs faster to balance the supply.

On an AC ship the variable DC has to be made. The traditional way is the Ward-Leonard drive: an AC motor turns a DC generator, and varying the generator's field varies the voltage it feeds to the winch motor. Its modern replacement is a thyristor converter that rectifies the ship's AC to a controlled DC.

The no-field condition

If the shunt field circuit of a running motor opens, through a broken connection or a corroded terminal, the motor does not stop. Residual magnetism in the poles keeps it turning, but it is far too weak to make a proper back emf. So the armature current rises sharply. Lightly loaded, the motor speeds up dangerously. Heavily loaded, the weak field cannot give enough torque, and the current climbs until the overcurrent protection trips. A no-field trip disconnects the motor the moment its field is lost.

On board: DC motors survive in older deck machinery, cranes and lifts. Check the brushes and commutator at each inspection, prove the no-field and overspeed trips, and never run a series motor without its load.
Check yourself
1. What does the commutator do in a DC motor?
It reverses the current in each armature coil as it passes a pole, so the torque always acts the same way.
2. Why is a DC motor's starting current so high without a starter?
At standstill there is no back emf, so only the small armature resistance limits the current.
3. Why must a series motor never run without load?
Its speed rises sharply as load falls, and unloaded it can run away to a dangerous speed.
4. What are interpoles for, and why are they in series with the armature?
They correct the flux at the brushes so commutation is spark-free; being in series, their correction grows with the load current that causes the distortion.
5. How do you run a shunt motor above its base speed?
Weaken its field with the field rheostat.
6. What happens if a running shunt motor's field opens, and what protects it?
Its armature current rises sharply, because residual magnetism gives too little back emf. Lightly loaded it races; heavily loaded it draws a huge current; a no-field trip disconnects it.

Going for your ETO CoC oral?

The full DC machines notes (T03), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Fernandez, E.A. Marine Electrical Technology, chapter 7, DC machines: field poles bolted to the frame with shims to set the air gap (7.2, p.222); the commutator (7.4, p.224); armature reaction, shaped pole tips and compensating windings (7.5-7.7, p.226-228); interpoles midway between the main poles, in series with the armature (7.8, p.229); back emf proportional to speed and field strength (7.17.1, p.252); armature reaction in a motor and adjusting the brushes for least sparking (p.255); the shunt motor's nearly constant speed (7.18, p.255-256); the no-field condition and the no-field trip (7.18.1, p.256-257); speed control above base by field resistance and below base by armature resistance (7.18.2, p.257-258); the series motor, its runaway with no load and the small shunt field fitted against it (7.19, p.258-260); compound motors, cumulative and differential (7.20, p.260-261).
  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014): DC commutator motors for deck machinery where speed control is needed (p.73); the Ward-Leonard drive for lifts, cranes and winches, and the thyristor controller that replaced it (p.87-88, Figures 4.15 and 4.16).
  • Wadhwa, C.L. Basic Electrical Engineering, chapter 6, DC machines: construction (6.2, p.245), emf equation, armature reaction and commutation (6.3, p.247 to 251), classification of DC machines (6.4, p.253), DC shunt and series motors and the speed equation (6.7.1 and 6.7.2, p.261 to 263), the DC motor starter (6.7.3, p.264).
  • Elec-Buddy notes: T03 Electric Motors (DC shunt and series motors), T09 Ship Machinery (deck machinery).
  • The lab's motor is a model, not a maker's machine: 37 kW, 220 V, about 190 A, 1,000 rpm base speed, four poles with interpoles, with a five-stud face-plate starter and overcurrent and overspeed trips at the lab's own settings. Its proportions are typical, not taken from a drawing. An automated test checks that it behaves as the sources describe.