At the instant a motor is switched on, its rotor is not turning and there is no back emf to hold the current down. The only thing limiting the current is the impedance of the windings, so a cage motor started straight onto the full supply takes about five to seven times its full-load current until it runs up to speed.
On shore, the grid hardly notices. On a ship, that surge flows through the generator's own impedance, and the busbar voltage dips while it lasts. Lights flicker, and other equipment can drop out on its undervoltage release. So small motors, up to about 20 kW where the switchboard can stand it, are started direct on line, and larger ones such as thrusters, cargo pumps and compressors are started at reduced voltage.
Every starter switches the motor with a contactor, an electrically held three-pole switch worked from start and stop buttons, and protects it with an overcurrent relay that trips the contactor if the motor is overloaded.
One contactor connects the motor straight to the full supply. It is cheap, simple and gives the full starting torque. The price is the full starting surge. The motor itself is not harmed by it, unless it is started and stopped many times in a short period.
For a motor designed to run in delta, with all six winding ends brought out. It starts with the windings connected in star, then a timer switches them to delta once the motor is near full speed.
In star, each winding has the phase voltage across it, 440 ÷ √3 = 254 V, instead of the full 440 V. The current in each winding falls by √3, and because in star the line current is the winding current while in delta it is √3 times it, the line current falls by √3 × √3 = 3.
The sequence uses three contactors: the main contactor KM1, the star contactor KM2 and the delta contactor KM3. Press start and KM1 and KM2 close; the motor runs up in star. The timer, usually set to 5 to 9 seconds depending on the size of the motor, then opens KM2 and closes KM3. KM2 and KM3 are interlocked so they can never be closed together, which would short-circuit the supply.
Because the torque in star is only a third, a heavily loaded motor may change over well below full speed, and then the second surge, at the changeover, can be large. The lab shows this with a heavy pump load.
An autotransformer feeds the motor a reduced voltage from one of a few taps, such as 40, 50 or 65%, then switches it to the full supply. The starting current drawn from the supply falls with the square of the tap: a 50% tap gives a quarter of the DOL surge.
Example: a motor with a full-load current of 200 A. DOL, its starting surge is about 5 × 200 = 1,000 A. Star-delta brings it down to a third, about 330 A. A 50% autotransformer tap brings it to 0.5² × 1,000 = 250 A.
A soft starter uses pairs of thyristors in the supply lines, fired later or earlier in each half cycle, to raise the motor's voltage gradually from a low value to full. The current and torque build up smoothly, with no steps and no second surge. Once the motor is at full voltage the thyristors can be bypassed for normal running.
A soft starter controls the voltage, not the speed: a motor's speed is set by the supply frequency. To control speed, a variable frequency drive is needed.
| Starter | Starting current | Starting torque | Where it is used |
|---|---|---|---|
| Direct on line | About 5 to 7 × full load | Full | Small motors, up to about 20 kW |
| Star-delta | A third of DOL | A third of DOL | Pumps and fans that start lightly loaded |
| Autotransformer | Tap² × DOL | Tap² × DOL | Large motors; the tap can be chosen to suit the supply |
| Soft starter | Limited, and smooth | Built up smoothly | Where a smooth start matters |