Motor starters

Why a motor draws several times its running current at the start, and how DOL, star-delta, autotransformer and soft starters deal with the surge on a ship's generators.

Machines, page 3 of 65 min readUpdated 20 November 2026All 6 pages

A motor at rest draws several times its running current the moment it is switched on. The starter decides how that first surge is handled: all at once, in two steps, or gently. On a ship, where one or two generators carry everything, that choice decides whether the lights dip and other machinery trips.

An interactive motor starter loads here. It needs JavaScript; the sections below explain everything it shows.

Why a motor needs a starter

At the instant a motor is switched on, its rotor is not turning and there is no back emf to hold the current down. The only thing limiting the current is the impedance of the windings, so a cage motor started straight onto the full supply takes about five to seven times its full-load current until it runs up to speed.

On shore, the grid hardly notices. On a ship, that surge flows through the generator's own impedance, and the busbar voltage dips while it lasts. Lights flicker, and other equipment can drop out on its undervoltage release. So small motors, up to about 20 kW where the switchboard can stand it, are started direct on line, and larger ones such as thrusters, cargo pumps and compressors are started at reduced voltage.

Every starter switches the motor with a contactor, an electrically held three-pole switch worked from start and stop buttons, and protects it with an overcurrent relay that trips the contactor if the motor is overloaded.

Direct on line (DOL)

One contactor connects the motor straight to the full supply. It is cheap, simple and gives the full starting torque. The price is the full starting surge. The motor itself is not harmed by it, unless it is started and stopped many times in a short period.

Star-delta

For a motor designed to run in delta, with all six winding ends brought out. It starts with the windings connected in star, then a timer switches them to delta once the motor is near full speed.

In star, each winding has the phase voltage across it, 440 ÷ √3 = 254 V, instead of the full 440 V. The current in each winding falls by √3, and because in star the line current is the winding current while in delta it is √3 times it, the line current falls by √3 × √3 = 3.

Istart, star = ⅓ × Istart, DOL
and the starting torque, which goes with the voltage squared, falls to a third as well

The sequence uses three contactors: the main contactor KM1, the star contactor KM2 and the delta contactor KM3. Press start and KM1 and KM2 close; the motor runs up in star. The timer, usually set to 5 to 9 seconds depending on the size of the motor, then opens KM2 and closes KM3. KM2 and KM3 are interlocked so they can never be closed together, which would short-circuit the supply.

Stuck in star: if the changeover fails and a delta motor is left running in star on full load, each winding carries √3 times its rated current and the copper heats three times as fast. The line current, though, is no more than its normal full-load value, because the motor gives the same power in either connection. So the overload relays must be in the winding (phase) connections, where they see the overcurrent; relays in the line connections would let the motor burn.

Because the torque in star is only a third, a heavily loaded motor may change over well below full speed, and then the second surge, at the changeover, can be large. The lab shows this with a heavy pump load.

Autotransformer

An autotransformer feeds the motor a reduced voltage from one of a few taps, such as 40, 50 or 65%, then switches it to the full supply. The starting current drawn from the supply falls with the square of the tap: a 50% tap gives a quarter of the DOL surge.

Example: a motor with a full-load current of 200 A. DOL, its starting surge is about 5 × 200 = 1,000 A. Star-delta brings it down to a third, about 330 A. A 50% autotransformer tap brings it to 0.5² × 1,000 = 250 A.

Soft starter

A soft starter uses pairs of thyristors in the supply lines, fired later or earlier in each half cycle, to raise the motor's voltage gradually from a low value to full. The current and torque build up smoothly, with no steps and no second surge. Once the motor is at full voltage the thyristors can be bypassed for normal running.

A soft starter controls the voltage, not the speed: a motor's speed is set by the supply frequency. To control speed, a variable frequency drive is needed.

The starters compared
StarterStarting currentStarting torqueWhere it is used
Direct on lineAbout 5 to 7 × full loadFullSmall motors, up to about 20 kW
Star-deltaA third of DOLA third of DOLPumps and fans that start lightly loaded
AutotransformerTap² × DOLTap² × DOLLarge motors; the tap can be chosen to suit the supply
Soft starterLimited, and smoothBuilt up smoothlyWhere a smooth start matters
Check yourself
1. Why does a motor draw so much current at the moment it starts?
The rotor is at rest, so there is no back emf; only the impedance of the windings limits the current.
2. A delta motor's DOL starting current is 900 A. What will it draw started star-delta?
A third: about 300 A.
3. Why are the star and delta contactors interlocked?
If both closed together they would short-circuit the supply.

Going for your ETO CoC oral?

The full Motor starters notes (T03), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), chapter 4, motors and starters: starting current 5 to 8 times FLC (p.78); DOL for motors up to about 20 kW, the voltage dip from larger ones and undervoltage releases tripping, contactors and the overcurrent relay (p.79-80); star-delta, the KM1, KM2, KM3 sequence, the 5 to 9 s timer and the interlock (p.81); the one-third current and torque, and the √3 overcurrent and three times the heating of a delta motor left in star, and overcurrent relays fitted in the phase connections, not the line connections (p.82); autotransformer taps of 40, 50 and 65% and the x² starting current (p.82-83); soft starting with back-to-back thyristors, bypassed once at full voltage, and not a speed controller (p.84-85); the worked example of a 200 A motor started DOL, star-delta and on a 50% tap (p.85).
  • Fernandez, E.A. Marine Electrical Technology: the star-delta starter (12.4, p.448) and soft starters using thyristors (12.10, p.474).
  • Elec-Buddy notes: T03 Electric Motors.
  • The lab starts the motor of the Induction motor page, scaled to 90 kW, on a 625 kVA generator. The generator's transient reactance (0.15 per unit), the soft starter's ramp and its current limit of 3 times full load are illustrative; the star-delta timer is set to 6 s, inside Hall's 5 to 9 s. An automated test checks its figures against the page.