Induction motor

The rotating field, the squirrel cage rotor, why the rotor always slips a little behind, and why large motors need a starter.

Machines, page 2 of 69 min readUpdated 18 November 2026All 6 pages

Most of the motors on a ship are induction motors. Pumps, fans, compressors, purifiers, winches, thrusters: almost all of them. The induction motor needs no brushes and no electrical connection to its rotor at all, and that makes it simple, tough and very reliable.

An interactive 3D motor loads here. It needs JavaScript; everything it shows is also explained in the text below.

Construction

Switch the lab to Names and turn the motor round. A shipboard pump motor is built from the same few parts whatever its size.

PartWhat it does
FrameThe cast iron or steel body. Its fins carry heat away; the feet bolt it to the bedplate.
Stator coreA stack of thin steel sheets (laminations) with slots round the bore. Thin sheets keep the eddy current loss in the iron small.
Stator windingThree sets of insulated copper coils in the slots, one per phase, brought out to the terminal box.
RotorAnother laminated core on the shaft, carrying the cage: bars of copper or aluminium joined at each end by a short-circuiting ring. In small and medium motors the whole cage is aluminium, cast in one piece.
Air gapThe small clearance between rotor and stator. The field has to cross it to reach the rotor, so it is kept small.
End shields and bearingsHold the shaft centred in the bore. Usually ball or roller bearings, greased.
Fan and cowlA fan on the shaft blows air over the finned frame. A totally enclosed motor is cooled from the outside only.
Terminal boxWhere the supply cable is connected to the winding ends (U, V, W, with links for star or delta).

The rotor bars are usually set at a slight angle along the rotor (skewed). That makes the motor run more quietly and stops the rotor teeth locking against the stator teeth at start.

The rotating magnetic field

Each phase winding on its own makes a field that only pulses: it grows along that winding's axis, dies away, then grows the other way, sixty times a second on a 60 Hz supply. It does not move round.

The three windings are spaced a third of the way round from each other, and the three currents peak one after another, a third of a cycle apart. Add the three pulsing fields together at any instant and the result is one field of steady strength, 1.5 times the peak of one phase, pointing in a direction that moves on smoothly round the stator. The small chart beside the motor in the lab draws exactly this: three arrows that only grow and shrink on their own lines, and their sum, which turns.

In the lab, watch the stator teeth: the pale glow is the field, and the N and S tags ride on its poles. The phase coils light in turn, red, yellow, blue, as each current peaks.

Synchronous speed

The field turns at the synchronous speed. In one cycle of the supply it moves on by one pair of poles, so the more poles the winding has, the slower it turns.

Ns = 120 × f ÷ P
Ns = synchronous speed (rpm), f = supply frequency (Hz), P = number of poles. The 120 is 60 seconds × 2 poles per pair
Poles60 Hz50 Hz
23,600 rpm3,000 rpm
41,800 rpm1,500 rpm
61,200 rpm1,000 rpm
8900 rpm750 rpm

The poles are fixed by how the winding is laid in the slots, so a given motor has one synchronous speed for a given frequency. To change the speed of a cage motor, change the frequency (a variable frequency drive) or use a motor wound for two pole numbers.

Rotor currents and torque

Nothing is wired to the rotor. The turning field sweeps across the cage bars and induces a voltage in them, as in the secondary of a transformer. The end rings short-circuit the bars, so a large current flows. A current-carrying bar lying in a magnetic field feels a force, and the forces on all the bars together turn the rotor the same way as the field.

In the lab the bars glow orange where the field is inducing current in them. At standstill they glow hard. Once the motor is running they barely glow.

Slip

The rotor can never quite catch the field. If it did, the bars would be standing still relative to the field, nothing would be induced, and there would be no current and no torque. So it always runs slightly slower. Even on no load it has to slip a little, to make the torque that covers friction and windage. The difference is the slip.

s = (Ns − N) ÷ Ns × 100%
N = actual rotor speed. A 6-pole motor on 60 Hz running at 5% slip: Ns = 1,200 rpm, slip = 60 rpm, N = 1,140 rpm

Load the motor more and it slows a little, the slip grows, more current is induced in the cage and the torque rises to match. From no load to full load the speed falls by only a few percent, so the induction motor is treated as an almost constant speed machine. At full load the slip is typically 3 to 5%.

Torque against speed

The chart under the lab plots the torque the motor can make at each speed, beside the torque the pump needs. Read it from left to right, the way the motor runs up.

  • Starting torque (left edge): the torque at standstill. It must be more than the load needs to break away. The lab's motor starts with about 1.8 times its full-load torque.
  • Pull-out torque (the peak): the most the motor can give, about three times full-load torque in the lab. Load the shaft beyond it and the motor slows right down and stalls.
  • Running point: where the motor's curve crosses the load's. Below it the motor has torque to spare and speeds up; above it the load wins and it slows. It settles on the crossing, close to synchronous speed.

A centrifugal pump or fan needs little torque at low speed, and its load climbs steeply as the speed rises (the lab models it as rising with the square of the speed). That is why a pump motor runs up easily even on a reduced-voltage starter, and why a pump motor overloads quickly if it is made to run faster.

Starting current and starting methods

At standstill the slip is 100%: the field cuts the cage bars at full synchronous speed, the induced rotor current is huge, and the stator draws five to eight times its full-load current. The power factor is poor too: about 0.2 lagging at start. It is low again on no load, because the little current a running, unloaded motor draws is mostly the magnetising current for its field, which lags the voltage by nearly 90°. It rises to about 0.85 at full load. The current falls as the rotor gains speed.

For a small motor that surge does no harm. A large one dips the voltage of the whole switchboard, flickering the lights and possibly tripping other consumers on undervoltage. So the larger motors are started at reduced voltage.

StarterHow it worksStarting current
Direct on line (DOL)One contactor puts full voltage straight on the motor. Simple and cheap, used up to about 20 kW where the generators can take it.5 to 7 × full load. The voltage dip should stay within 10 to 15%.
Star-deltaThe winding starts in star, so each phase gets 1/√3 of the line voltage. A timer then changes it over to delta for running.One third of DOL. The starting torque is also one third.
AutotransformerA three-phase autotransformer feeds a tapped-down voltage, typically 50 to 80%, then full voltage once the motor is near speed. Used for large drives such as cargo pumps.x² × DOL at a tap of x: a 50% tap gives a quarter.
Soft starterThyristors switch on a little earlier in each half cycle, raising the voltage gradually from a low value, so the run-up is smooth.Held down by the ramp.
Variable frequency driveStarts the motor at low frequency and raises the frequency, with the voltage, over a set acceleration time, then controls its speed while running.Limited by the drive.

Try both starters in the lab. With direct on line the current meter shoots past five times full load. With star-delta the first surge is a third of that, and the second, at the changeover to delta, is still well below the direct-on-line one.

On board: every pump and fan has a starter panel with its contactor and overload relay. The larger ones have a star-delta arrangement: three contactors (main, star and delta) and a timer, with an interlock so the star and delta contactors can never close together.
Reversing the direction of rotation

The field turns in the order the phases reach their peaks. Swap any two of the three supply lines at the terminal box and that order reverses, so the field, and the motor, turn the other way. Try it in the lab with the motor stopped.

This matters every time a new supply is connected. A shore supply with the wrong phase sequence would turn every three-phase motor on board backwards, so the sequence is checked before the shore breaker is closed, and corrected by swapping two conductors if it is wrong.

Single phasing

If one of the three lines is lost while the motor runs (a blown fuse, a contactor contact that fails to make), the motor can keep turning on the other two. This is single phasing. The current in the remaining lines rises, the motor gets noisy from the uneven torque, and one winding can carry far more than its share, enough to burn it out while the line currents still look acceptable. A stopped motor will not restart on two lines: it just draws starting current and stalls. Motor overload relays therefore include a single phasing (unbalance) trip.

Check yourself
1. What is the synchronous speed of a 6-pole motor on 60 Hz?
120 × 60 ÷ 6 = 1,200 rpm.
2. Why can the rotor never run at synchronous speed?
At that speed the bars would not cut the field, so no current would be induced and there would be no torque.
3. A 4-pole motor on 60 Hz runs at 1,746 rpm. What is its slip?
Ns = 1,800 rpm; slip = (1,800 − 1,746) ÷ 1,800 = 3%.
4. Why do large motors need a special starter?
At standstill they draw five to eight times their full-load current, enough to dip the ship's voltage; the starter limits it.
5. How much does a star-delta starter cut the starting current and torque?
Both to one third of their direct-on-line values.
6. A pump motor runs backwards after a rewire. What do you change?
Swap any two of the three supply lines at the terminal box.

Going for your ETO CoC oral?

The full Induction motor notes (T03), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), chapter 4, motors and starters: construction, cage bars and short-circuiting rings in a laminated core (p.73-74); synchronous speed from frequency and pole pairs (p.76); reversing by swapping two supply lines, no torque at synchronous speed (p.77); starting current 5 to 8 times FLC, power factor about 0.2 at start, 0.5 on no load and 0.85 at full load, speed falling 1 to 5% from no load to full load, the torque-speed curve with full load at 3 to 5% slip, and the 6-pole, 5% slip example (p.78); DOL up to about 20 kW and the voltage dip (p.79-80); star-delta, one third of the current and torque (p.81-82); autotransformer taps and x² current (p.82-83); soft starting (p.84-85); single phasing (p.94-95). Phase sequence of a shore supply and the red, yellow, blue colours used in the lab (p.33).
  • Wadhwa, C.L. Basic Electrical Engineering: the rotating magnetic field, with its constant magnitude of 1.5 times one phase's maximum (7.2.2, p.280-282); construction, cast aluminium cages in small and medium motors (8.2, p.304); skewed rotor laminations (p.306); principle and slip (8.3, p.305); starting (8.6, p.315).
  • Fernandez, E.A. Marine Electrical Technology: centrifugal pumps and blowers, whose load rises steeply with speed (4.3.4.2, p.134); soft starters using thyristors (12.10, p.474).
  • Elec-Buddy notes: T03 Electric Motors.
  • The lab's motor is a model, not a maker's machine: a 30 kW, 440 V, 60 Hz cage motor run in delta, worked out from its equivalent circuit at every instant. Its figures were set to sit inside the ranges above (about 3.3% full-load slip, about 5.5 times full-load current at start, power factor 0.86 at full load), checked against them by an automated test. Its starting power factor (about 0.4) is higher than Hall's typical 0.2, so the lab does not show power factor.
  • Where sources disagree: Hall (p.78) gives the no-load power factor as about 0.5 lagging. Machine texts generally put it lower, about 0.1 to 0.3, since an unloaded motor's current is mostly magnetising current; the lab's equivalent circuit gives about 0.2 when it runs unloaded. The page says "low" and gives no figure.