Gas and fire detectors

Smoke, heat and flame detectors and how the fire panel knows a fire from a fault; catalytic, infrared, electrochemical and paramagnetic gas detectors; and the meter for enclosed space entry.

Sensors and instrumentation, page 6 of 63 min readUpdated 4 November 2026All 6 pages

Fire gives itself away three ways: smoke, heat and flame. Each fire detector looks for one of them. Gas detectors look for something you usually cannot see or smell at all: a flammable gas, a toxic one, or too little oxygen.

An interactive compartment with fire detectors loads here. It needs JavaScript; the sections below explain everything it shows.

Smoke detectors
Optical (photoelectric)
A light source and a light sensor inside a dark chamber, set so the light does not normally reach the sensor. Smoke drifting in scatters the light onto it, and the detector alarms. Good for slow, smouldering fires.
Ionisation
A tiny radioactive source makes the air in a chamber conduct a small current. Smoke particles get in the way and the current falls, and the detector alarms. Quick to fast, flaming fires.
Heat detectors
Fixed temperature
Alarms when it reaches a set temperature, by a bimetal or a link that melts. Used where smoke detectors would give false alarms: galleys, laundries, some machinery spaces.
Rate of rise
Alarms when the temperature climbs faster than normal, whatever the temperature is. It ignores the slow warm-up of a space but catches a fire early.

Heat detectors are made so that a slow warm-up does not set them off: on a gentle rise they should not operate below about 54 °C, and they should operate before 78 °C. Many fixed-temperature bimetal detectors are set at 78 °C.

Flame detectors

A flame gives off ultraviolet and infrared light that flickers. A flame detector watches for that light and alarms within a fraction of a second. Used where an open fire can start fast, such as round the main engine, the purifiers and the boiler front.

Detection loops and the fire alarm panel

The detectors are wired in loops or zones back to the fire alarm panel, with manual call points at the exits. The panel watches each loop all the time. It tells a fire from a broken wire or a short circuit, and shows which zone or which detector raised the alarm. The panel is normally on the bridge, with a repeater in the engine control room.

Gas detectors
Catalytic (flammable gas)
A small heated bead with a catalyst on it. Flammable gas burns on the bead and heats it, and the change in its resistance gives the reading in % LEL, the share of the lowest concentration that could explode. It needs oxygen to work.
Infrared
Many gases absorb infrared light at their own wavelength. Shine that wavelength through the sample and measure how much is lost. Used for hydrocarbons and CO2, and it works without oxygen.
Electrochemical (toxic gas, oxygen)
The gas reacts at an electrode inside a small cell and makes a current in proportion to how much there is. Used for oxygen, hydrogen sulphide and carbon monoxide.
Paramagnetic (oxygen)
Oxygen, unlike most gases, is pulled into a magnetic field. Analysers use that to measure oxygen accurately, for example in an inert gas system.
Before anyone enters an enclosed space, the atmosphere is tested with a portable meter for oxygen, flammable gas, hydrogen sulphide and carbon monoxide. Ships must carry one. Never go in on a reading taken only at the hatch.
Check yourself
1. Why is a heat detector, not a smoke detector, fitted in the galley?
Cooking makes smoke and steam that would set off a smoke detector; a heat detector ignores them.
2. A catalytic gas detector reads zero in a tank full of inert gas. Is the tank safe?
No. The catalytic bead needs oxygen to burn the gas, so in an inert atmosphere it can read zero even with flammable gas present, and there is too little oxygen to breathe anyway.
3. What does a rate-of-rise detector respond to?
How fast the temperature is rising, not the temperature itself.

Going for your ETO CoC oral?

The full Gas and fire detectors notes (T15), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • SOLAS Chapter II-2, regulation 7, and the FSS Code, chapter 9: fixed fire detection and fire alarm systems, with the control panel on the navigation bridge or in a continuously manned control station.
  • SOLAS Chapter XI-1, regulation 7: ships carry a portable atmosphere testing instrument for enclosed space entry, measuring at least oxygen, flammable gases or vapours, hydrogen sulphide and carbon monoxide.
  • Fernandez, E.A. Marine Electrical Technology: fire detection initiating devices, smoke, heat and flame (p.890); heat detectors operating above about 54 °C on a slow rise and before 78 °C, and bimetal detectors set at 78 °C (p.892).
  • Elec-Buddy notes: T15 Fire Fighting (detector types and working principles, the detection loop and its end-of-line resistor), T14 Bridge Equipment II and T19 Tankers (catalytic, infrared and electrochemical gas detectors, the paramagnetic oxygen analyser).
  • The lab puts an optical smoke detector and a combined fixed and rate-of-rise heat detector on one loop. The fixed element operates at 78 °C, as Fernandez gives below; the smoke threshold (5% obscuration per metre), the rate-of-rise setting (8 °C a minute) and the four scenarios are illustrative. An automated test checks which detector each scenario sets off.