Control loops

The parts of a control loop, open and closed loop, on-off control, and the 4 to 20 mA and 0.2 to 1.0 bar signals that join the parts.

Control and automation, page 1 of 63 min readUpdated 4 November 2026All 6 pages

Most of the engine room looks after itself. Temperatures, pressures, levels and viscosities are held where they should be by control loops: a sensor, a controller and something that acts, working round and round without anyone touching them.

An interactive jacket cooling water loop loads here. It needs JavaScript; the sections below explain everything it shows.

Elements of a control loop
PartWhat it doesExample: jacket cooling water temperature
ProcessThe thing being controlledThe engine's cooling water
MeasurementThe sensor and transmitter reading itA PT100 and its transmitter
Set pointThe value you wantFor example 85 °C
ControllerCompares the measurement with the set point and decides what to doA controller in the alarm and control system
Final elementActs on the processA three-way valve sending more or less water through the cooler

The difference between the set point and the measurement is the error. The controller's whole job is to act so that the error goes to zero, and stays there as conditions change.

Open loop and closed loop
Open loop
Acts without checking the result. A timer that runs a pump for ten minutes does not know whether the tank is full. Simple, but it cannot correct itself.
Closed loop
Measures the result and feeds it back. The controller sees the error and corrects it. Almost every process control on board is closed loop.
On-off control

The simplest controller: fully on below the set point, fully off above it, with a small dead band between so it does not switch on and off constantly. A thermostat or a compressor's pressure switch works this way. The value swings up and down within the dead band.

Where the value must be held steady, the controller instead moves its output smoothly in proportion to the error and how it changes. That is PID control, on its own page.

Standard signals

The sensor, controller and final element talk to each other by standard signals. The most common is 4 to 20 mA: 4 mA means the bottom of the range and 20 mA the top. Starting at 4 rather than 0 means a broken wire, which gives 0 mA, can be told apart from a reading at the bottom of the range. Pneumatic valves are driven by air at 0.2 to 1.0 bar.

Manual, automatic and the unattended engine room

Every loop on board can be run by hand. On the controller's front, or in the control system, you switch it from automatic to manual and set the valve yourself. That is the open loop from the lab: it holds the valve where you put it and does nothing when the load changes, so it is only for starting up, testing, or riding out a fault in the measurement.

Closed loops are what let a ship run with nobody in the engine room at night. SOLAS Chapter II-1, Part E (regulations 46 to 54) sets what a periodically unattended machinery space needs: automatic control of the machinery, alarms that reach the duty engineer wherever they are, and protection that stops machinery before it damages itself. Each of those starts with a control loop, a sensor and an alarm point.

Check yourself
1. What is the error in a control loop?
The difference between the set point and the measurement.
2. Why does the standard signal start at 4 mA, not 0?
So a broken wire (0 mA) is told apart from a reading at the bottom of the range.
3. Is a timer running a pump for ten minutes open or closed loop?
Open loop: it does not measure the result.

Going for your ETO CoC oral?

The full Control loops notes (T07), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • IDC Technologies, Practical Instrumentation for Automation and Process Control (2004), chapter 1: basic measurement and control concepts (1.1, p.1), measuring instruments and control valves as part of the overall control system (1.7, p.22); the smart instrument and 4 to 20 mA (7.1, p.247).
  • Elec-Buddy notes: T07 Control Systems and PLC (open and closed loops, on-off control, the 4 to 20 mA live zero, 0.2 to 1.0 bar pneumatic signals), T06 Sensors (transmitters).
  • SOLAS Chapter II-1, Part E, regulations 46 to 54: additional requirements for periodically unattended machinery spaces.
  • The lab is a teaching model, not a particular engine: the water temperature follows the valve with a lag of 20 s and a dead time of 4 s, and the numbers are chosen so the behaviour is easy to see. An automated test checks that it behaves as this page describes.