An interactive jacket cooling water loop loads here. It needs JavaScript; the sections below explain everything it shows.
| Part | What it does | Example: jacket cooling water temperature |
|---|---|---|
| Process | The thing being controlled | The engine's cooling water |
| Measurement | The sensor and transmitter reading it | A PT100 and its transmitter |
| Set point | The value you want | For example 85 °C |
| Controller | Compares the measurement with the set point and decides what to do | A controller in the alarm and control system |
| Final element | Acts on the process | A three-way valve sending more or less water through the cooler |
The difference between the set point and the measurement is the error. The controller's whole job is to act so that the error goes to zero, and stays there as conditions change.
The simplest controller: fully on below the set point, fully off above it, with a small dead band between so it does not switch on and off constantly. A thermostat or a compressor's pressure switch works this way. The value swings up and down within the dead band.
Where the value must be held steady, the controller instead moves its output smoothly in proportion to the error and how it changes. That is PID control, on its own page.
The sensor, controller and final element talk to each other by standard signals. The most common is 4 to 20 mA: 4 mA means the bottom of the range and 20 mA the top. Starting at 4 rather than 0 means a broken wire, which gives 0 mA, can be told apart from a reading at the bottom of the range. Pneumatic valves are driven by air at 0.2 to 1.0 bar.
Every loop on board can be run by hand. On the controller's front, or in the control system, you switch it from automatic to manual and set the valve yourself. That is the open loop from the lab: it holds the valve where you put it and does nothing when the load changes, so it is only for starting up, testing, or riding out a fault in the measurement.
Closed loops are what let a ship run with nobody in the engine room at night. SOLAS Chapter II-1, Part E (regulations 46 to 54) sets what a periodically unattended machinery space needs: automatic control of the machinery, alarms that reach the duty engineer wherever they are, and protection that stops machinery before it damages itself. Each of those starts with a control loop, a sensor and an alarm point.