An interactive pneumatic control valve loads here. It needs JavaScript; the sections below explain everything it shows.
Most control valves on board are moved by a pneumatic diaphragm actuator: air pressure on a large diaphragm pushes against a spring and moves the stem. Raise the air pressure and the stem moves one way; lower it and the spring pushes it back. Electric and hydraulic actuators are used too, especially on large valves.
If the air supply is lost, the spring drives the valve to one end of its travel. Which end is chosen for safety when the valve is specified.
| Action | On loss of air | Example |
|---|---|---|
| Fail open (air to close) | The spring opens it | A cooling water valve, so the engine still gets cooling |
| Fail closed (air to open) | The spring closes it | A fuel or steam supply, so it shuts off |
Friction in the valve's packing and the force of the flow can stop the stem going exactly where the signal asks. A positioner, mounted on the actuator, measures the stem's actual position through a linkage and adjusts the air to the actuator until the position matches the signal. Smart positioners also take the 4 to 20 mA signal directly, report the position back, and can be calibrated automatically.