Control valves and positioners

Globe, butterfly and three-way valve bodies, the pneumatic diaphragm actuator, fail-open and fail-closed action, and what a positioner adds.

Control and automation, page 5 of 62 min readUpdated 4 November 2026All 6 pages

The control valve is where the loop meets the pipe. The controller decides; the valve does it, opening or closing to let more or less fluid through. It has two parts: the valve body in the pipe, and the actuator that moves it, often with a positioner on top.

An interactive pneumatic control valve loads here. It needs JavaScript; the sections below explain everything it shows.

The valve body
Globe valve
A plug on a stem moves up and down against a seat. Precise control, so it is the usual control valve.
Butterfly valve
A disc that turns a quarter turn across the pipe. Compact, for large pipes such as sea water.
Three-way valve
Mixes or splits a flow between two paths, such as the cooler and its bypass in a temperature loop.
The actuator

Most control valves on board are moved by a pneumatic diaphragm actuator: air pressure on a large diaphragm pushes against a spring and moves the stem. Raise the air pressure and the stem moves one way; lower it and the spring pushes it back. Electric and hydraulic actuators are used too, especially on large valves.

Fail-safe action

If the air supply is lost, the spring drives the valve to one end of its travel. Which end is chosen for safety when the valve is specified.

ActionOn loss of airExample
Fail open (air to close)The spring opens itA cooling water valve, so the engine still gets cooling
Fail closed (air to open)The spring closes itA fuel or steam supply, so it shuts off
The positioner

Friction in the valve's packing and the force of the flow can stop the stem going exactly where the signal asks. A positioner, mounted on the actuator, measures the stem's actual position through a linkage and adjusts the air to the actuator until the position matches the signal. Smart positioners also take the 4 to 20 mA signal directly, report the position back, and can be calibrated automatically.

Check yourself
1. Should a fuel supply valve fail open or fail closed?
Fail closed, so the fuel shuts off if the air is lost.
2. What does a positioner do?
It measures the stem's actual position and adjusts the air until it matches the signal.
3. Which valve body splits a flow between a cooler and its bypass?
A three-way valve.

Going for your ETO CoC oral?

The full Control valves and positioners notes (T07), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • IDC Technologies, Practical Instrumentation for Automation and Process Control (2004), chapter 6, control valves: principles (6.1, p.205), sliding stem valves (6.2, p.206), rotary valves (6.3, p.220), actuators and positioners (6.7, p.237).
  • Elec-Buddy notes: T07 Control Systems and PLC (valve actuators, fail-safe action, positioners), T06 Sensors (SIPART PS2 positioner calibration).
  • The lab is a diaphragm actuator against a spring, 0.2 to 1.0 bar for full travel. The friction that makes the stem stick without a positioner is set at 8% of travel, an illustrative figure. An automated test checks its fail-safe action and the positioner.