I/P converter

How an I/P converter turns a controller's current signal into air pressure for a valve, with its flapper and nozzle, relay and feedback.

Control and automation, page 4 of 62 min readUpdated 4 November 2026All 6 pages

The I/P converter joins electrical control to air-driven valves. Controllers speak in current, 4 to 20 mA. Many control valves on a ship are moved by air pressure. The I/P converter, current to pressure, turns one into the other.

An interactive I/P converter loads here. It needs JavaScript; the sections below explain everything it shows.

Input and output signals
Bottom of rangeTop of range
Signal in4 mA20 mA
Air out0.2 bar1.0 bar

It also needs a steady supply of clean, dry instrument air, usually at about 1.4 bar or more, which it throttles down to the output pressure the signal asks for.

Flapper-nozzle principle

Air flows out through a small nozzle, and a thin flapper sits just in front of it. The closer the flapper is to the nozzle, the more it blocks the air and the higher the pressure behind the nozzle. The input current flows through a coil next to a magnet, and the force on the coil moves the flapper. More current, the flapper closer, a higher pressure.

That small pressure is boosted by a relay inside, which supplies the volume of air the valve needs, and a feedback bellows makes the output pressure track the current accurately.

Position in the control loop

Between the controller and a pneumatic control valve, often mounted on the valve itself. Many modern valves use a smart positioner instead, which takes the 4 to 20 mA signal directly and does the I/P conversion and the positioning in one unit.

On board: temperature control valves for cooling water and lube oil, steam control valves, and fuel viscosity control.
Check yourself
1. What air pressure does an I/P converter give at 12 mA?
Halfway along: 0.6 bar (12 mA is halfway between 4 and 20).
2. What moves the flapper?
The force on the coil carrying the input current, beside a magnet.
3. What does it need besides the signal?
A supply of clean, dry instrument air.

Going for your ETO CoC oral?

The full I/P converter notes (T07), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • IDC Technologies, Practical Instrumentation for Automation and Process Control (2004), chapter 6: actuators and positioners operation (6.7, p.237).
  • Elec-Buddy notes: T07 Control Systems and PLC (how the I/P converter works: flapper and nozzle, relay and feedback bellows; 4 to 20 mA in, 0.2 to 1.0 bar out), T06 Sensors (the SIPART smart positioner).
  • The lab converts 4 to 20 mA into 0.2 to 1.0 bar in a straight line, the ranges on this page; IDC gives the usual pneumatic control range as 3 to 15 psi (section 6.7, page 6.46 in the book's chapter numbering), the same span. The flapper and nozzle are drawn schematically. An automated test checks the conversion.