Refrigeration controls

How a provisions or reefer plant runs itself on a thermostat, solenoid valves and pressure switches, and what each safety trip is telling you.

Control and automation, page 6 of 63 min readUpdated 20 November 2026All 6 pages

The refrigeration engineer looks after the gas; the ETO looks after the controls. A provisions plant or a reefer plant runs itself on a handful of switches: a thermostat, a solenoid valve, pressure switches and a timer. When it stops, it is usually one of those that stopped it, and finding which is an electrical job.

An interactive cold room plant loads here. It needs JavaScript; the sections below explain everything it shows.

The cycle, in one paragraph

The compressor draws low-pressure refrigerant gas out of the evaporator in the cold room and pushes it, hot and at high pressure, to the condenser, where cooling water or air takes its heat and it turns to liquid. The liquid passes through an expansion valve into the evaporator, where it boils at low pressure and takes heat out of the room. The controls decide when liquid is allowed into each room's evaporator, and when the compressor runs.

The controls that run it
ControlWhat it does
Room thermostatOpens the room's liquid solenoid valve when the room is too warm, and shuts it when the room is cold enough.
Liquid solenoid valveLets liquid refrigerant into that room's evaporator, or stops it.
LP control switchStarts and stops the compressor on suction pressure, and resets itself. A typical setting cuts out at about 1.4 bar and cuts back in at about 2.8 bar.

The thermostat does not switch the compressor directly. When the room is cold, its solenoid shuts; the compressor keeps running and pumps the evaporator down until the suction pressure falls to the LP control's cut-out, and stops. When the room warms, the solenoid opens, liquid reaches the evaporator, the suction pressure rises to the cut-in, and the compressor starts. The circuit is also arranged so the compressor cannot start unless a room's solenoid is open, so a leaking solenoid valve cannot make it cycle on its own.

The safety trips

Three switches protect the compressor, and each needs a manual reset, so somebody has to look at why it tripped.

TripActs at, for R22Usual cause
HP, high pressureAbout 24 bar on the dischargeCondenser cooling lost: water off or fouled, or air fan stopped
LP, low pressureAbout 1 bar on the suctionThe backup if the LP control fails to stop the compressor
Oil differential pressureOil pressure less than about 1.2 bar above suctionOil pump or oil level; a start delay lets the pressure build first
A sign to recognise: a compressor that keeps stopping and starting every minute or two, on its LP control, is often short of refrigerant. Too little liquid reaches the evaporator to hold the suction pressure up.
Check yourself
1. The cold room is cold enough. Which control acts first?
The thermostat shuts the room's solenoid valve; the compressor then pumps down and stops on its LP control.
2. The compressor has stopped on its HP trip. Where do you look first?
At the condenser's cooling: the water supply or the air fan.
3. Why do the safety trips need a manual reset?
So that someone finds the cause before the compressor runs again.

Going for your ETO CoC oral?

The full Refrigeration controls notes (T09), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Fernandez, E.A. Marine Electrical Technology, chapter 25, miscellaneous systems, refrigerating machinery (25.7, from p.993): the compressor safety devices, an HP switch at up to about 24 bar for R22, an LP switch at about 1 bar and an oil differential pressure switch at about 1.2 bar with a starting time delay, all with manual reset (25.7.3, p.995); the LP control switch with automatic reset, cut-out at about 1.4 bar and cut-in at about 2.8 bar, and no start unless a room's solenoid valve is open (25.7.4, p.996).
  • The lab uses Fernandez's switch settings. The room, the thermostat's -18 and -16 °C, and the rates at which the pressures and the temperature change are illustrative. An automated test runs each fault and checks which switch stops the compressor.