Flow sensors

How each type of flowmeter works: orifice plate, rotameter, turbine, positive displacement, vortex, magnetic, ultrasonic and Coriolis, and which one measures mass.

Sensors and instrumentation, page 4 of 63 min readUpdated 4 November 2026All 6 pages

A flowmeter answers how much is passing. Most measure how fast the fluid moves and multiply by the pipe's area to give volume per hour. One type measures the mass directly. On a ship the flow that matters most is fuel: what is bunkered and what the engines burn.

An interactive orifice plate flowmeter loads here. It needs JavaScript; the sections below explain everything it shows.

Differential pressure flowmeters

Put a plate with a hole in it, an orifice plate, across the pipe. The fluid speeds up through the hole and its pressure drops, and the faster the flow, the bigger the drop. Measure the pressure difference across the plate and you have the flow. The flow goes with the square root of the pressure difference: four times the difference means twice the flow. So the transmitter's signal, which follows the pressure difference, has to have its square root taken before it reads as flow; at half flow the pressure difference is only a quarter of full scale. For the same reason an orifice meter is poor at low flows, where the pressure difference becomes too small to measure well.

Variable area flowmeters

A float sits in a vertical tube that widens towards the top. The flow lifts the float until the gap round it is big enough to let the flow past, so the float's height is the flow rate, read on a scale on the glass. Called a rotameter. Simple, and needs no power.

Turbine and positive displacement meters
Turbine
A small rotor spins in the flow. A pick-up counts the blades as they pass, and the pulse rate is the flow.
Positive displacement
Gears or rotors that trap a fixed volume at a time and pass it on. Count the turns and you have the volume. Accurate for oils, and common as fuel consumption meters.
Vortex
A blunt bar across the pipe sheds swirls, first one side then the other. They come faster as the flow rises, and a sensor counts them. No moving parts.
Electromagnetic flowmeters

Coils outside the pipe make a magnetic field across it. A conducting liquid flowing through the field is a conductor moving through a field, so a voltage appears across it, picked up by two electrodes in the pipe wall. The voltage is in proportion to the speed. It works only with liquids that conduct, such as water and sea water, not oil.

Ultrasonic flowmeters

Sound pulses are sent diagonally across the pipe, with the flow and against it. The pulse going with the flow arrives slightly sooner, and the difference in time gives the speed. Some types clamp on the outside of the pipe, so they can be fitted without cutting into it.

Coriolis mass flowmeters

The fluid passes through a tube that is kept vibrating. Moving mass in a vibrating tube twists it very slightly, and the amount of twist is in proportion to the mass flowing. So a Coriolis meter measures mass directly, whatever the fluid's density, viscosity or temperature, and it can read the density too.

On board: bunkers are bought by mass, so Coriolis meters are used for bunker deliveries and for accurate fuel consumption.
Comparison
TypeWorks byGood for
Orifice (DP)Pressure drop across a restrictionClean liquids, gases, steam
RotameterFloat height in a tapered tubeLocal reading, no power
TurbineCounting rotor bladesClean liquids
Positive displacementCounting fixed volumesOils, fuel consumption
VortexCounting swirls behind a barLiquids, gases, steam
MagneticFaraday voltage in a conducting liquidWater, sea water
UltrasonicTiming sound with and against the flowLarge pipes, clamp-on checks
CoriolisTwist of a vibrating tubeMass flow: bunkers and fuel
Check yourself
1. The pressure drop across an orifice plate rises four times. What has the flow done?
It has doubled, because flow goes with the square root of the pressure difference.
2. Why would a magnetic flowmeter not work on a fuel oil line?
It needs a liquid that conducts. Oil does not, so no voltage is induced.
3. Which meter measures mass directly?
The Coriolis meter.

Going for your ETO CoC oral?

The full Flow sensors notes (T06), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • IDC Technologies, Practical Instrumentation for Automation and Process Control (2004), chapter 5: differential pressure flowmeters and the square-root relationship (5.2, p.146), variable area (5.4, p.165), oscillatory flow measurement including vortex and turbine meters, the pick-up counting blades as they pass (5.5 and 5.5.2, from p.167), magnetic flowmeters (5.6, p.179), positive displacement (5.7, p.185), ultrasonic (5.8, p.189), mass flow meters including Coriolis (5.9, p.192).
  • Elec-Buddy notes: T06 Sensors and Instrumentation (Coriolis, turbine, vortex and orifice flowmeters).
  • The lab is an orifice plate whose pressure drop goes with the square of the flow (IDC 5.2, p.146), read by a DP transmitter that is linear in pressure drop. The full-scale drop of 250 mbar is illustrative. An automated test checks the square law and the square root.