An interactive oil bath with three temperature sensors loads here. It needs JavaScript; the sections below explain everything it shows.
Join two wires of different metals at one end and heat that joint, and a small voltage appears between the two free ends. This is the Seebeck effect. The voltage depends on the difference in temperature between the hot joint and the far ends, so the instrument reading it also has to know the temperature at its own end. The common type K gives about 41 µV for every degree.
A thermocouple needs no power supply and stands very high temperatures, so it is the sensor in the hot places.
The resistance of a pure metal rises steadily as it warms. A resistance temperature detector is a fine platinum wire or film; pass a small current through it, measure its resistance, and you have its temperature. The standard one is the PT100: 100 Ω at 0 °C, rising to about 138.5 Ω at 100 °C.
An RTD is accurate and stable across the temperatures machinery runs at, and it is the most common temperature sensor on board.
A thermistor is a small bead of semiconductor whose resistance changes far more with temperature than a metal's does. Most have a negative coefficient (NTC): their resistance falls as they warm. The positive kind (PTC) works the other way, and some are made to stay low until a set temperature and then rise very sharply.
That sharp rise makes a PTC thermistor a switch rather than a gauge. Buried in a motor's winding and wired to a relay, it trips the motor when the winding itself gets too hot, whatever the cause.
Two strips of metals that expand by different amounts are bonded together. When the strip warms, one side grows more than the other and the strip bends. That movement can turn a pointer, or open and close a contact.
A bulb filled with liquid or gas sits in the hot medium, joined by a thin capillary tube to a gauge. As the bulb warms, its filling expands and the pressure moves a pointer. The gauge can be a few metres away from the bulb, and nothing electrical is involved. The ordinary glass thermometer works the same way, with the liquid rising up the stem.
Everything warm gives off infrared radiation, and the hotter it is the more it gives off. An infrared thermometer or thermal camera measures that radiation, so it reads a temperature from a distance, without touching the surface.
| Type | What changes | Typical place on board |
|---|---|---|
| Thermocouple | Makes its own small voltage | Exhaust gas temperatures |
| RTD (PT100) | Resistance rises steadily | Bearings, oil, water, windings |
| Thermistor | Resistance changes sharply | Motor winding protection |
| Bimetallic | Bends | Thermostats, overload relays, dial gauges |
| Filled system | Expands and pushes a pointer | Local gauges |
| Infrared | Reads the radiation given off | Hot spot checks on running plant |
A sensor's own output, a few millivolts or a change of a few ohms, is too small and too easily disturbed to send across an engine room. A transmitter beside the sensor turns it into a standard signal, usually a current of 4 to 20 mA: 4 mA at the bottom of the range, 20 mA at the top. A PT100 transmitter ranged 0 to 200 °C sends 12 mA at 100 °C.
A current is used because it is the same all the way round the loop, whatever the length and resistance of the cable. The range starts at 4 mA, not zero, so that a reading of zero can only mean a fault: a broken wire or a dead transmitter. That raised starting point is called a live zero.