Level sensors

How a tank's level is measured on a ship: sight glass and sounding, float, hydrostatic pressure and the bubbler, capacitance and conductivity probes, ultrasonic, radar and the vibrating fork.

Sensors and instrumentation, page 3 of 63 min readUpdated 4 November 2026All 6 pages

A ship is full of tanks, and every one needs its level known. Fuel, lube oil, fresh water, ballast, bilge wells, the boiler drum. Some sensors give a continuous reading, others only switch at one level for an alarm. Which is used depends on the liquid and on what the reading is for.

An interactive tank with a level transmitter loads here. It needs JavaScript; the sections below explain everything it shows.

Sight glasses and sounding

The simplest level gauge is a glass tube or a window joined to the tank at top and bottom, so the liquid in the glass stands at the same height as in the tank. A boiler's gauge glass works this way. Tanks without one are measured by sounding: lowering a weighted tape down the sounding pipe and reading where it comes out wet.

Float type

A float rides on the surface and moves an arm, a magnet or a switch. Moving a magnet past reed switches gives a reading in steps; tipping a switch gives an alarm at one level.

On board: bilge high level alarms, fresh water and service tank level switches.
Hydrostatic pressure

The pressure at the bottom of a tank depends on how much liquid is above it: pressure equals the height times the liquid's density times g. Measure that pressure and you know the height, as long as you know the density. Get the density wrong and the reading is wrong in proportion: a transmitter set up for fresh water, reading a tank of oil at 850 kg/m³, shows the level 15% low. A pressure transmitter at the bottom, or a differential one between bottom and top in a closed tank, does exactly this.

A bubbler does the same from above: air is blown gently down a pipe to the bottom of the tank, and the pressure needed to push bubbles out of the end equals the liquid's pressure there.

On board: ballast and fuel tank gauging, often shown on the remote tank gauging screen, and the boiler drum level.
Capacitance and conductivity
Capacitance probe
A rod and the tank wall form a capacitor. Liquid round the rod changes the capacitance in proportion to how much of the rod is covered. Works in oil and other liquids that do not conduct.
Conductivity probe
Two bare electrodes. When a conducting liquid such as water or sea water touches both, a small current flows and the switch operates. It cannot work in oil.
Ultrasonic and radar

A transmitter at the top of the tank sends a pulse down, and times how long the echo takes to come back from the surface. Distance is speed times time, halved for the trip down and back, and the level follows from the tank's height.

Ultrasonic
Uses sound. Simple, but vapour, foam and temperature change the speed of sound and so the reading.
Radar
Uses microwaves, which vapour and temperature barely affect. Accurate enough for the cargo tanks of tankers.
Vibrating fork

A small tuning fork is kept vibrating at its natural frequency. When liquid covers it, the vibration changes and the switch operates. With no moving parts to stick, it makes a reliable high or low level switch.

Check yourself
1. A pressure transmitter at the bottom of a tank reads the level. What else must it know?
The density of the liquid, since the pressure equals height times density times g.
2. Why would a conductivity probe be no use in a fuel oil tank?
Oil does not conduct, so no current flows between the electrodes. A capacitance probe works in oil.
3. Why is radar used in tanker cargo tanks rather than ultrasonic?
Vapour and temperature change the speed of sound and so upset an ultrasonic reading; they barely affect microwaves.

Going for your ETO CoC oral?

The full Level sensors notes (T06), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • IDC Technologies, Practical Instrumentation for Automation and Process Control (2004), chapter 3: sight glasses and gauging rods (3.2, p.52), buoyancy (3.3, p.54), hydrostatic pressure including the bubbler (3.4, p.56), ultrasonic (3.5, p.65), radar (3.6, p.70), vibration switches (3.7, p.71), electrical methods: capacitance and conductivity (3.9, p.78).
  • Elec-Buddy notes: T06 Sensors and Instrumentation (float, capacitance, conductivity, ultrasonic and radar level sensors and where they are used on board).
  • The lab gauges a 4 m tank by the pressure at its bottom, p = ρgh, with a transmitter calibrated for fresh water at 1,000 kg/m³, and a float switch at 3.6 m. Sea water is taken as 1,025 kg/m³; the diesel oil, at 850 kg/m³, is an illustrative figure. An automated test checks its figures against the page.