Pressure sensors

Gauge, absolute and differential pressure, and how each sensing element works: Bourdon tube, diaphragm, bellows, strain gauge, capacitive and piezoelectric, plus the pressure switch.

Sensors and instrumentation, page 2 of 63 min readUpdated 4 November 2026All 6 pages

Every pressure sensor has something that moves. Pressure pushes on an element, the element moves a tiny amount, and that movement is turned into a pointer reading or an electrical signal. The types below differ in what the element is, and in how its movement is read.

An interactive hydrophore tank loads here. It needs JavaScript; the sections below explain everything it shows.

Gauge, absolute and differential

A pressure is always measured against something, and the three kinds are named after what that is.

KindMeasured againstExample on board
Gauge (bar g)The air around it. Reads zero when open to the air.Almost every engine room gauge: lube oil, fuel, cooling water, starting air
Absolute (bar a)A perfect vacuum. Reads about 1 bar when open to the air.Condenser vacuum, barometric pressure
DifferentialA second pressure. Reads the difference between two points.A filter clogging, flow across an orifice, a tank's level
Mechanical elements
Bourdon tube
A curved, flattened metal tube closed at one end. Pressure inside tries to straighten it, and the tip's movement turns a pointer through a small gear. The ordinary dial gauge on a pipe.
Diaphragm
A thin, flexible disc that bulges as pressure rises. Good for low pressures and, with a seal, for dirty or corrosive fluids.
Bellows
A small metal concertina that stretches as pressure rises. It moves further than a diaphragm for the same pressure, so it suits low ranges and pressure switches.
Electrical transducers
Strain gauge
A fine resistance pattern bonded to a diaphragm. As the diaphragm flexes, the pattern stretches and its resistance changes. A bridge circuit turns that into a signal, usually 4 to 20 mA. The most common pressure transmitter on board.
Capacitive
The diaphragm is one plate of a capacitor. As pressure moves it closer to a fixed plate, the capacitance changes. Very sensitive, so it suits differential pressure transmitters.
Piezoelectric
A crystal that makes a small charge when it is squeezed. It responds only to changing pressure, not steady pressure, so it is used where pressure changes fast: the cylinder pressure of a running engine.
The pressure switch

A pressure switch uses the same elements, usually a bellows or diaphragm, but instead of a reading it gives a contact that opens or closes at a set pressure. It has two settings: the set point, where it operates, and the differential, how far the pressure has to come back before it resets. Without that gap, the contact would chatter on and off around the set point.

On board: starting a standby pump on low pressure, a compressor's start and stop, low lube oil pressure alarms and shutdowns.
Check yourself
1. A gauge open to the air reads zero. Is it gauge or absolute?
Gauge. An absolute gauge would read about 1 bar, the pressure of the atmosphere.
2. Why can a piezoelectric sensor not measure the steady pressure in a lube oil line?
It only makes a signal while the pressure is changing. Steady pressure gives nothing, so it is used for fast-changing pressure such as a cylinder's.
3. What is the differential on a pressure switch for?
It sets how far the pressure must come back before the switch resets, so the contact does not chatter around the set point.

Going for your ETO CoC oral?

The full Pressure sensors notes (T06), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • IDC Technologies, Practical Instrumentation for Automation and Process Control (2004), chapter 2: principles of pressure measurement (2.1, p.25), mechanical elements such as the Bourdon tube, diaphragm and bellows (2.3, p.28), electrical elements such as the strain gauge, capacitive and piezoelectric sensors (2.4, p.38).
  • Elec-Buddy notes: T06 Sensors and Instrumentation (gauge, absolute and differential pressure; the sensing elements; pressure switch set point and differential; the DP transmitter).
  • The lab is a hydrophore tank kept between a cut-in of 3 bar and a cut-out of 4 or 5 bar by a pressure switch, with a transmitter ranged 0 to 10 bar g to 4 to 20 mA. The switch settings and the tank's rates of rise and fall are illustrative; atmospheric pressure is taken as 1.013 bar. An automated test checks the switch and the transmitter.