Power and power factor

Real, reactive and apparent power, the power triangle, lagging and leading, and why a poor power factor costs current, with a worked 500 kW example.

Electrical fundamentals, page 6 of 63 min readUpdated 4 November 2026All 6 pages

Not all the current a load draws does useful work. Motors and transformers need some current just to keep their magnetic fields up. Power factor says how much of the current is doing real work, and it decides how hard the generators and cables are working.

An interactive generator panel loads here. It needs JavaScript; the sections below explain everything it shows.

Active, reactive and apparent power
PowerUnitWhat it is
Real (P)kWDoes the work: turns pumps, heats, lights.
Reactive (Q)kVArBuilds the magnetic fields in motors and transformers, and is handed back every half cycle. It does no work, but it is current all the same.
Apparent (S)kVAVolts times amps: what the generator and cables actually have to carry.

They form a right-angled triangle: kW along the bottom, kVAr up the side, and kVA the long side. The angle between kW and kVA is φ, the angle by which the current lags the voltage.

power factor = cos φ = kW ÷ kVA
and kVA = √(kW² + kVAr²)
The horse and barge analogy

A horse on a towpath pulls a barge along a canal with a rope. Because the horse walks beside the canal, the rope pulls at an angle. Only part of the pull moves the barge forward; the rest pulls it sideways towards the bank and is wasted. The forward part is the kW, the whole pull on the rope is the kVA, and the more the rope angles out, the worse the power factor.

Where the picture stops: the horse's sideways pull is simply lost, but reactive power is not lost. It flows back and forth between the generator and the load's magnetic fields every half cycle. What it costs is current, and current means heat in every cable and winding it passes through.
Lagging and leading

Coils make the current lag the voltage, so a ship's load, mostly motors, has a lagging power factor, typically about 0.8. Capacitors make it lead. A load that is purely resistive, such as a heater, has a power factor of 1.

Effects of a low power factor

A generator's windings heat with current, and current follows kVA whatever the power factor. So alternators are rated in kVA, usually at 0.8 lagging, and a poor power factor uses up their capacity without giving more kW.

Example: a 500 kW load on 440 V. At a power factor of 0.8 it needs 500 ÷ 0.8 = 625 kVA, and the current is 625,000 ÷ (1.732 × 440) ≈ 820 A. At a power factor of 1 the same 500 kW needs only about 656 A. At 0.8 the current has a reactive part as well, 820 × 0.6 ≈ 492 A, at right angles to the working 656 A. Because they are at right angles they add as the sides of a triangle, √(656² + 492²) = 820 A, not 1,148 A. The reactive part does no work, but the generator and cables carry the full 820 A and heat with all of it.

On board: the power factor meter on each generator panel, and the kW and kVAr meters, show how the load is made up. When generators run in parallel, kW is shared through the governors and kVAr through the AVRs.
Check yourself
1. A load takes 400 kW and 500 kVA. What is its power factor?
400 ÷ 500 = 0.8.
2. Why are alternators rated in kVA, not kW?
Their windings heat with current, which follows kVA whatever the power factor.
3. Is a ship's power factor usually lagging or leading, and why?
Lagging, because most of the load is motors, which are coils.

Going for your ETO CoC oral?

The full Power and power factor notes (T11), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), p.3: power factor = cos φ = P/S, with P = V × I × cos φ, Q = V × I × sin φ and S = V × I; p.50: a ship's load is typically about 0.8 lagging.
  • Wadhwa, C.L. Basic Electrical Engineering, chapter 1: power in an AC circuit and the phase angle between voltage and current (1.6.3, p.60 to 61).
  • Elec-Buddy notes: T11 Power Factor, T01 Alternators (kVA rating, load sharing of kW and kVAr).
  • Drawn for Elec-Buddy: the horse and barge picture is a teaching analogy, with its limit stated on the page.
  • The lab is the page's example: one 440 V generator rated 625 kVA, which is 500 kW at 0.8, supplying a load whose kW and lagging power factor you set. An automated test checks its figures against the page.