Three-phase

Why ships use three-phase, phase sequence, star and delta connections, line and phase voltage and the √3, and three-phase power.

Electrical fundamentals, page 5 of 62 min readUpdated 4 November 2026All 6 pages

A ship's generators make three supplies at once. Three windings, set a third of a turn apart, give three equal voltages a third of a cycle apart. That is three-phase, and it is what the main switchboard distributes.

An interactive three-phase motor in star or delta loads here. It needs JavaScript; the sections below explain everything it shows.

Generation of three-phase voltages

An alternator's stator has three sets of windings spaced 120° round it. As the rotor's field sweeps past, each set gives a sine wave, and each wave is 120° behind the one before. The three lines are usually named L1, L2 and L3, or R, Y and B.

The order in which the three reach their peaks is the phase sequence. Swap any two lines and the sequence reverses, and so does every motor fed from them.

Advantages of three-phase supply
  • Steady power. In a balanced three-phase load the total power is constant through the cycle, so a motor runs smoothly.
  • A rotating field for free. Three currents 120° apart in three windings set up a magnetic field that turns by itself. An induction motor needs nothing else to start.
  • Less copper. Three-phase carries more power for the weight of cable than single-phase.
Star

In star, one end of each winding is joined at a common point, the star point, and the other ends go out to the lines. The voltage across one winding is the phase voltage; the voltage between two lines is the line voltage, and it is larger by √3, about 1.732, because the two phase voltages it is made from are 120° apart.

Vline = √3 × Vphase
a 440 V star system has 440 ÷ 1.732 ≈ 254 V from each line to the star point. Line and phase current are equal.
Delta

In delta, the three windings are joined end to end in a triangle, and the lines come from the corners. Each winding sits straight across two lines, so line and phase voltage are the same. Now it is the current that differs: the line current is √3 times the current in each winding.

Three-phase power
P = √3 × VL × IL × cos φ
VL, IL = line voltage and current; cos φ = power factor. The same formula for star and delta.

Example: a 440 V motor drawing 50 A at a power factor of 0.85 takes 1.732 × 440 × 50 × 0.85 ≈ 32.4 kW.

On board: the 440 V system is usually insulated, with no star point earthed, so a single earth fault does not trip anything; the insulation monitor on the switchboard warns you of it instead.
Check yourself
1. What is the phase voltage of a 440 V star system?
440 ÷ 1.732 ≈ 254 V.
2. A motor runs backwards after a cable is reconnected. What happened?
Two lines were swapped, reversing the phase sequence. Swap any two back.
3. In delta, which is larger: line current or phase current?
Line current, by √3.

Going for your ETO CoC oral?

The full Three-phase notes, the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Wadhwa, C.L. Basic Electrical Engineering, chapter 3, three phase supply: three-phase circuits (3.1, p.160), star circuits (3.2, p.164), delta circuits (3.3, p.169), power measurement (3.4, p.172).
  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), p.3: in star, line voltage is √3 times phase voltage (440 V gives 254 V); balanced three-phase power is √3 × VL × IL × cos φ; the same 10 Ω windings take 25.4 A per line in star and 76.2 A in delta, three times as much.
  • Elec-Buddy notes: T12 Cables and Earthing (the insulated 440 V system and the insulation monitor).
  • The lab uses the page's motor example, 440 V at a power factor of 0.85, with its windings in star or delta and the relations above. An automated test checks its figures against the page.