An interactive 24 V lamp circuit loads here. It needs JavaScript; the sections below explain everything it shows.
A metal wire is full of electrons that are free to move. Connect it to a supply and they drift along it, all together. That flow of charge is the current, measured in amperes (A). One ampere is one coulomb of charge passing a point every second.
Charge only flows when something pushes it. That push is the voltage, or potential difference, measured in volts (V). One volt means one joule of energy is given to every coulomb of charge that passes. A generator or a battery provides it; a load uses it up.
Every material resists the flow a little or a lot. Resistance is measured in ohms (Ω). Metals such as copper resist very little and are conductors. Rubber, PVC, mica and dry air resist so much that almost nothing flows, and they are insulators.
A wire's resistance depends on three things: the material, its length and its cross-section. A longer wire has more resistance and a thicker one has less, as a long thin pipe passes less water than a short wide one.
For annealed copper, the usual cable conductor, ρ is about 1.72 × 10-8 Ω m at 20 °C. So one core of 1.5 mm² cable, 30 m long, has 1.72 × 10-8 × 30 ÷ 1.5 × 10-6 = 0.34 Ω.
The resistance of a metal also rises as it warms up: copper's by about 0.4% for every degree. So an overloaded cable heats up, its resistance rises with the heat, and that adds still more heat. The same effect is how a resistance temperature sensor works.
A cable's resistance is small, but the load current flows through all of it, out along one core and back along the other. Some of the supply voltage is used up driving the current through the cable, and the load gets what is left. That loss is the voltage drop: the current times the resistance of both cores.
Example, as in the lab: a 24 V 48 W lamp fed through a 30 m run of 1.5 mm² copper. The two cores have 0.69 Ω between them and the current is 1.89 A, so the cable takes 1.3 V and the lamp gets 22.7 V. Make the run 100 m and the cable takes 3.9 V; the lamp, with less voltage and so less current, gives about 34 W instead of 48 W. A bigger cable size is the cure. Long runs on board are sized for voltage drop as well as for current.
Think of a pump pushing water round a closed loop of pipe. The pump's pressure is the voltage, the water flowing is the current, and a narrow section of pipe is a resistance. More pressure, more flow; a narrower pipe, less flow. That picture is right as far as it goes.
Power is how fast energy is used, measured in watts (W). In a DC circuit it is the voltage times the current. Energy is power over time; a 1 kW heater run for one hour uses 1 kWh.
Example: a 24 V lamp drawing 2 A uses 24 × 2 = 48 W.