Ohm's and Kirchhoff's laws

Ohm's law, series and parallel circuits, voltage drop on a long cable, and Kirchhoff's current and voltage laws used for real fault-finding.

Electrical fundamentals, page 2 of 63 min readUpdated 4 November 2026All 6 pages

Three laws solve almost every circuit you will fault-find. Ohm's law links voltage, current and resistance in one part. Kirchhoff's two laws say what happens where wires meet and round any closed loop.

An interactive 220 V distribution board loads here. It needs JavaScript; the sections below explain everything it shows.

Ohm's law

For a metal conductor at a steady temperature, the current through it is in proportion to the voltage across it. Double the voltage and the current doubles. The constant that links them is the resistance.

V = I × R
so I = V ÷ R and R = V ÷ I

Example: a heater element of 44 Ω on 220 V draws 220 ÷ 44 = 5 A.

Series circuits

Resistances one after another carry the same current. Their resistances add, and the supply voltage is shared between them in proportion to their resistance.

R = R₁ + R₂ + R₃
series: same current through each, voltages add up to the supply

A long cable is in series with its load. Its own resistance takes part of the voltage before the load gets any: this is the voltage drop, and it is why a motor at the end of a long run can start badly.

Parallel circuits

Loads connected side by side all have the same voltage across them, and each takes its own current. The total current is the sum of the branch currents. Adding another branch makes the combined resistance smaller, not larger.

1 ÷ R = 1 ÷ R₁ + 1 ÷ R₂ + 1 ÷ R₃
parallel: same voltage across each, currents add up to the total
On board: every load on a switchboard is in parallel. Each sees the full bus voltage, and switching one off does not affect the others. Switching more on raises the total current the generator has to supply.
Kirchhoff's current law

At any point where wires meet, the current flowing in equals the current flowing out. Charge does not pile up or vanish.

Example: a feeder carries 30 A to a distribution board, and two outgoing circuits take 12 A and 10 A. The third circuit must be taking 30 − 12 − 10 = 8 A.

Kirchhoff's voltage law

Go round any closed loop and add up the voltages: the rises from sources equal the drops across the loads. All the push the supply gives is used up somewhere round the loop.

Example: a 24 V circuit with a lamp reading 21 V across it and a cable drop of 1 V. The missing 2 V is being lost somewhere else in the loop, often at a corroded joint or a loose terminal. That is how you find it with a voltmeter.

A bad joint does more than waste volts. Every watt it takes, I²R, becomes heat in one small place. In the lab, the board normally draws about 30 A. Let its feeder joint work loose to 1 Ω and the current falls to 26 A; the joint takes 26 V of the supply and turns about 680 W into heat, and every heater on the board gets only 191 V. The same current through a tight joint of a thousandth of an ohm makes under a watt.

Check yourself
1. Two 10 Ω resistors in parallel. What is the combined resistance?
5 Ω: 1 ÷ R = 1/10 + 1/10 = 2/10.
2. Three lamps are in series and one fails open. What happens to the others?
They all go out: there is only one path, and it is broken.
3. Into a junction come 15 A and 5 A; one wire leaves carrying 12 A. What does the other carry?
15 + 5 − 12 = 8 A out.

Going for your ETO CoC oral?

The full Ohm's and Kirchhoff's laws notes, the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Wadhwa, C.L. Basic Electrical Engineering, chapter i: Ohm's law (i.8, p.8), Kirchhoff's laws (i.9, p.11), series, parallel and series-parallel circuits (i.10, p.13 to 18); chapter 2, network theory (2.2, p.119).
  • The lab uses only those laws: a 220 V board fed through 0.1 Ω of feeder cable and a line joint whose resistance you set, with three heaters sized to take 12, 10 and 8 A at 220 V, the current-law example above. An automated test checks its figures against the page.