A variable frequency drive sets a motor's speed by changing the frequency it is fed. An induction motor's speed follows the supply frequency, so a drive that can make any frequency can run the motor at any speed, and start it gently too.

An interactive variable frequency drive loads here. It needs JavaScript; the sections below explain everything it shows.

Rectifier, DC link and inverter
  1. Rectifier: turns the ship's fixed-frequency AC into DC.
  2. DC link: a bank of large capacitors that store the DC and keep it steady.
  3. Inverter: six IGBTs switch the DC on and off thousands of times a second, in a pattern that builds a three-phase supply of whatever frequency and voltage the motor needs. This is pulse width modulation.
V/f control

The motor's speed follows the frequency: Ns = 120 × f ÷ P. But if the frequency were lowered on its own, the motor's windings, which have less reactance at lower frequency, would draw too much current and the iron would saturate. So the drive lowers the voltage in step with the frequency, keeping the ratio of the two roughly constant. That keeps the motor's magnetic field, and so its torque, at the right level at every speed.

Applications on board
  • Soft starting: the drive starts at a low frequency and ramps up, with none of the large starting current of a direct start.
  • Speed control: winches, cranes, thrusters and propulsion run at exactly the speed needed.
  • Saving energy on pumps and fans, whose power falls very steeply as their speed is reduced. Running an engine room fan a little slower saves a large share of its power.
Practical considerations
  • Harmonics: the drive's rectifier draws its current from the ship's supply in pulses, not as a smooth sine wave. That distorts the supply voltage, mostly at the 5th and 7th harmonics (300 and 420 Hz on 60 Hz), and can cause flickering lights and upset electronic equipment elsewhere on the board.
  • Motor insulation: the sharp voltage edges stress a motor's winding insulation more than a plain sine wave.
The DC link stays charged after the drive is switched off. Its capacitors can hold a lethal voltage for several minutes. Wait the time marked on the drive and prove the DC link dead before you touch anything inside.
Check yourself
1. Name the three stages inside a VFD.
Rectifier, DC link and inverter.
2. Why does the drive lower the voltage when it lowers the frequency?
To keep the motor's magnetic field right: at low frequency the windings would otherwise draw too much current.
3. Why wait before working inside a drive that is switched off?
The DC link capacitors can still hold a lethal charge.

Going for your ETO CoC oral?

The full Variable frequency drives notes (T08), the quiz bank and the questions MMD surveyors have actually asked, each with a model answer, are in the Elec-Buddy app.

Start your free trial

Sources

Where the figures on this page come from, by book and printed page or by regulation.

  • Fernandez, E.A. Marine Electrical Technology, chapter 17, propulsion (p.657): frequency converters with IGBTs.
  • Hall, D.T. Practical Marine Electrical Knowledge, 3rd ed. (2014), p.89-90: a drive chopping large currents creates harmonic voltages in the supply, at the 5th, 7th, 11th and 13th harmonics (a 5th up to about 20% of the fundamental, a 7th about 14%), causing insulation stress from voltage spikes, flickering lights and malfunction of electronic equipment.
  • Elec-Buddy notes: T08 Electronics and T03 Electric Motors (VFD stages, V/f control, harmonics, motor insulation stress, DC link discharge before work), T11 Power Factor (harmonics).
  • The lab feeds the motor of the Induction motor page at the drive's frequency, with the voltage in proportion (440 V at 60 Hz), and finds where its torque meets a centrifugal pump's, which rises with the square of speed. Fernandez notes that pump and blower loads rise steeply with speed (4.3.4.2, p.134). An automated test checks the speed and power.